Configuration / setup
Page 12
AC_F110_BA_02_1346
November 2014
6.4.8
COMMUNICATION (OPTIONAL) - 8
Functions as described below deal with hardware that is not part of the standard delivery. Programming of these functions
does not have any effect if this hardware has not been installed.
Baud Rate (optional) - 81:
For external control, following communication speeds can be selected: 1200 - 2400 - 4800 - 9600 baud
Bus address (optional) - 82:
For RS485 communication, a unique identity can be attributed to every F110. This address can vary from 1-250 (consult the
description in the protocol).
ASCII / RTU (optional) - 83:
The Modbus communication protocol is executed according ASCII or RTU mode.
Protocol (optional) - 84:
Select here the type of communication protocol to be used.
6.4.9
OTHERS – 9
Type of model - 91:
Serial number - 93:
Version software - 92:
For support and maintenance, it is important to have information about the characteristics of the display/totaliser. Your
supplier will ask for this information in case of a serious breakdown or a desired extension of the system.
Password - 94:
All SETUP-values can be password protected. This protection is disabled with value 0000 (zero). Up to and including 4 digits
can be programmed, e.g. 1234.
Time - 95:
The actual time is available for the operator and communication purposes. The time has to be inserted in accordance with the
24 hours pattern; HH:MM:SS (hours:minutes:seconds).
Date - 96:
The actual date is available for the operator and communication purposes. The date has to be inserted in accordance with this
pattern: YY-MM-DD (year.month.day).
Tag number - 97:
For identification of the unit and communication purposes, a unique tag number of maximum 7 digits can be entered.