Configuration / setup 

Page 10

 

AC_F110_BA_02_1346

 

November 2014

 

6.4.3

 

DISPLAY - 3 

Function - 31 

The large 17 mm digits can be set to display total or flow rate digits at operator level. When total is selected, both total and 

flow rate are displayed simultaneously. When flow rate is selected, total will be displayed after pressing select. 

 

6.4.4

 

POWER MANAGEMENT - 4 

As the F110 is normally battery powered, the user will have the concern of reliable measurement over a long period of time. 

The F110 has several smart power management functions to extend the battery life time significantly. Two of these functions 

can be set: 

 

LCD refresh - 41: 

The calculation of the display information influences the power consumption significantly. When the application does not 

require a fast display update, we advise you to select a slow refresh rate. 

NOTE:

 

No information will be lost; every pulse will be counted and the output signals are not influenced. 

The following can be selected: 

Fast - 1 sec - 3 sec - 15 sec - 30 sec. 

Example: battery life time with a coil pick-up and FAST update: About 3 years. Battery life time with a coil pick-up and 1 sec 

update: About 8 years. 

Please note that after a button has been pressed by the operator, the display refresh rate will be FAST during the initial 30 

seconds. 

 

Battery mode - 42: 

The unit has two modes: operational or shelf. When shelf is selected, you can store the unit for several years; it will not count 

pulses, the display is switched off but all settings are stored. In this mode, power consumption is extremely low. Normally, the 

mode will be operational. 

 

6.4.5

 

FLOW METER - 5 

Signal - 51: 

The F110 is able to handle several types of signals. The type of flow meter pickup / signal is selected in software with SETUP 

51. 

Type of signal 

Explanation 

Resistance 

Power consumption 

Remark 

NPN 

Standard NPN input 

100K pull-up 

Relative high 

(open collector) 

NPN – LP 

NPN with low pass filter 

100K pull-up 

Relative high 

(open collector) less 

sensitive 

REED 

Reed-switch input 

1M pull-up low 

 

 

REED – LP 

Reed-switch with low 

pass filter 

1M pull-up low 

 

Less sensitive 

PNP 

Standard PNP input 

100K pull-down 

Relative high 

 

PNP – LP 

PNP input with low pass 

filter 

100K pull-down 

Relative high 

Less sensitive 

NAMUR 

Standard Namur input 

1K pull-down 

High 

External power required 

NAMUR – LP 

Namur with low pass 

filter 

1K pull-down 

High 

Ext. power required; less 

sensitive 

COIL HI 

High sensitive coil input 

Very low 

Sensitive for signal and 

disturbance 

COIL LO 

Low sensitive coil input 

Very low 

Normal sensitivity 

 

Maximum frequency - 52: 

Enter here the maximum frequency the flow meter might generate. It is advised to enter a little higher frequency than will 

ever be generated. 

 

Summary of Contents for MN Series

Page 1: ...Model F110 Display Totalizer AC_F110_BA_02_1346 November 2014 Instruction and operation manual...

Page 2: ...Model F110 Display Totalizer Page II AC_F110_BA_02_1346 November 2014...

Page 3: ...ated total 4 5 5 Display of time and date 4 5 6 Low battery level 4 6 Configuration setup 5 6 1 In general 5 6 2 SETUP level 5 6 3 Scrolling through SETUP 6 6 3 1 Selection of functions group and func...

Page 4: ...iew 15 7 5 2 Voltage supply flow meter pick up 15 7 5 3 Pulse output 16 7 5 4 External power supply 5 30VAC DC 16 7 5 5 Analog output 16 7 5 6 Inputs 17 7 5 7 Option communication printer RS232 RS485...

Page 5: ...UNIT THE INSTALLER HAS TO DISCHARGE HIMSELF BY TOUCHING A WELL GROUNDED OBJECT 1 2 Safety guidelines and measures Check mains supply and type plate before installation Check all connections settings a...

Page 6: ...and appendices are exclusively meant for electricians technicians These provide a detailed description of all software settings and hardware installation guidance Three kinds of pictograms appear in t...

Page 7: ...tery powered and intrinsically safe The F110 is designed to be implemented in many types of applications For that reason a SETUP level is available to configure your display totalizer best according t...

Page 8: ...the flow rate value is too high to be displayed The arrows indicate the increase decrease of the flow rate 5 3 Resetting the totalizer The value for total can be initialised To do so press CLEAR twic...

Page 9: ...en the housing Take careful notice of the Safety rules instructions and precautionary measures in the leading chapters of this manual This chapter describes the daily use of the F110 These instruction...

Page 10: ...ion the next main function is selected by scrolling through all active sub functions e g 1 11 12 13 14 1 2 3 31 etc 6 3 2 TO CHANGE OR SELECT A VALUE a Press briefly PROGRAM starts flashing b Select o...

Page 11: ...te 21 Unit L m3 kg lb GAL ton bbl no unit 3 Display 31 Function total flow rate 42 Battery mode operation shelf 4 Power management 41 LCD update fast 1sec 3sec 15sec 30sec 52 Maximum frequency 1 9 999...

Page 12: ...f pulses generated by the flow meter per selected measurement unit per cubic meter e g The more accurate the K factor the more accurate the functioning of the system will be Number of decimals display...

Page 13: ...erated per unit by the flow meter Enter here the number of pulses generated by the flow meter per selected measurement unit e g per litre The more accurate the K factor the more accurate the functioni...

Page 14: ...ate will be FAST during the initial 30 seconds Battery mode 42 The unit has two modes operational or shelf When shelf is selected you can store the unit for several years it will not count pulses the...

Page 15: ...ich the output should generate a 20mA mostly at maximum possible rate The number of decimals displayed is according to setup 24 The time and measuring units L min e g are according setup 21 and 22 but...

Page 16: ...used 6 4 9 OTHERS 9 Type of model 91 Serial number 93 Version software 92 For support and maintenance it is important to have information about the characteristics of the display totaliser Your suppl...

Page 17: ...DENTAL CONTACT IS NO LONGER ASSURED WHEN THE HOUSING COVER IS REMOVED OR THE PANEL CABINET HAS BEEN OPENED DANGER FROM ELECTRICAL SHOCK TRAINED PERSONNEL MAY ONLY OPEN THE HOUSING TAKE CAREFUL NOTICE...

Page 18: ...F BY TOUCHING A WELL GROUNDED OBJECT THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH THE EMC GUIDELINES ELECTROMAGNETIC COMPATIBILITY DO GROUND THE ALUMINIUM CASING PROPERLY OPTION HA HU AS INDICATED I...

Page 19: ...eters electronics converters etc as it is not a power output All energy used by the flow meters pick up influences the battery lifetime directly it is strongly advised to use a zero power pickup as a...

Page 20: ...5 4 EXTERNAL POWER SUPPLY 5 30VAC DC connectors 6 7 5 30 volt AC DC connect an external power supply to these terminals For a DC supply connect the to terminal 6 and the to terminal 7 7 5 5 ANALOG OUT...

Page 21: ...selections can be made COIL LO sensitivity from about 20mV or COIL HI sensitivity from about 5mV Pulse signal NPN PNP The F110 is suitable for flow meters which have a pulse output that is equal or a...

Page 22: ...at an external power supply is required 7 5 7 OPTION COMMUNICATION PRINTER RS232 RS485 See the manufacturer s plate A full serial computer control and driving in accordance with RS232 length of cable...

Page 23: ...as advised by the silica gel supplier 8 2 Battery lifetime Is influenced by several issues Type of pick up see chapter 7 5 6 NPN and PNP inputs consume more energy than coil inputs Analog output sign...

Page 24: ...or pulse bounce elimination available Flow meter supply voltage 3 2 VDC Remark For NAMUR and some signal pick ups external power to flow meter is required Analog output 4 20mA 10 bits resolution scale...

Page 25: ...SETUP 51 Sensitivity of coil input SETUP 51 and paragraph 7 5 5 Proper grounding of the F110 paragraph 7 4 Use screened wire for flow meter signals and connect screen to terminal 9 Pulse output does n...

Page 26: ...ecimals K factor 0 26 calculation pulses 10 27 cut off time 30 sec 3 Display 31 function total 4 Power man 41 LCD new 1 sec 42 mode operational 5 Flow meter 51 signal coil lo 52 max frequency 9999 Hz...

Page 27: ...discovery and at seller s option return of such meters or parts to seller f o b its factory THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES WHATSOEVER INCLUD...

Page 28: ...Harmlessness declaration www badgermeter de 13 RETURN OF GOODS FOR REPAIR HARMLESSNESS DECLARATION Please refer to our claims return form harmlessness declaration under https www badgermeter de en se...

Reviews: