Software menu
Page 59/62
LMS_MDS2000_BA_99_1002
Preset quantity:
4 litres = 400 pulses
Quantity dispensed:
4,1 lt. = 410 pulses
Difference:
0,1 lt. = 10 pulses
10 will be the calibration factor to introduce in the system
ENTER
ENTER
ENTER
By default all the I/O units have the same address (ID) N° 0 corresponding to
solenoid drivers (hose reels) 10 to 8. For the installation with multi I/O units (more
than 8 hose reels), each I/O must have its own address to be identified by the
network. Power up each I/O successively and change their address. For example
ID Nr. 1 for solenoid drivers (hose reels) 9 to 16.
ENTER
ENTER
The network dialogs now with this I/O unit 1 for hoses 9 to 16.
ENTER
Return to customer configure menu at the exit prompt. To return to the user screen,
press twice
ENTER
.
Select Hose
01
Pulse count
10
System Menu
Change I/O ID
Change ID I/O
From 0 to 1
System Menu
Exit