Badger Meter Impeller Data Industrial 3100 Series User Manual Download Page 21

Communication

RS-485 COM Port Configuration

The RS-485 is very simple to configure .
1 .  Select the communications type: Modbus or BACnet .
2 .  Choose the BAUD Rate: Auto, 300, 1200, 2400, 9600, 19200, 38400, or 76800 to match the rest of the devices on the 

network . The factory default of 9600 is recommended for most systems . The lower the baud rates have greater stability, 

and greater tolerance of wiring and other hardware issues .

3 .  Configure the Modbus or BACnet are described in there respective sections .

Modbus

Network: RS485

Baud Rate: Selectable

Protocol: RTU or ASCII

Addresses: 001 to 248

Slave only

Read Input Registers 30001- 39999 (Function “04”)

Data Type: IEEE 754 Float (ABCD – CDAB)

Each variable is stored in two Modbus registers; lowest byte in the first and highest in the second .

Only the variable value is transmitted .

The associated units of measure must be manually configured in the receiving Modbus device .

Flow 1 Rate 

(Input Register 30002 + 30003)

Flow 2 Rate 

(Input Register 30004 + 30005)

Flow 1 Total 

(Input Register 30006 + 30007)

Flow 2 Total 

(Input Register 30008 + 30009)

BACnet

The Model 3100 can be configured to communicate on a BACnet RS-485 MSTP (Master Slave Token Passing) system . 

Configuration is via the front panel key pad .
The following settings are required
•  Baud Rate: [9600;19200;38400; or 76800] . The recommended factory default is 9600 .
•  MSTP Address: [0-127] . Each device must have a unique address .
•  MSTP MAX master: [0-127] . This range must be greater than the highest address on the network .
•  Device Instance: [00000000-99999999] . This is a unique identifier for each device in the system .

Object Name

I/O  (Write/Read)

Object Type

Object ID

Units

BACnet Address

I/O

Analog Value

AV1

BACnet BaudRate

I/O

Multi-State

MSV1

See Note 1

Flow 1 Rate

O

Analog Input

AI1

Same as Displayed

Flow 2 Rate

O

Analog Input

AI2

Same as Displayed

Flow 1 Total

O

Analog Input

AI3

Same as Displayed

Flow 2 Total

O

Analog Input

AI4

Same as Displayed

Note 1: 0 = Auto, 1 = 9600, 2 = 19200, 3 = 38400, 4 = 76800

Note 2: Units of measure are selected by installer from a list of pre-programmed units, or as custom units created by the 

installer . BACnet will transmit in the same units as displayed on the Model 3100 front panel LCD . 

Programming 

Page 21 

August 2014

CTL-UM-001026-EN-04

Summary of Contents for Impeller Data Industrial 3100 Series

Page 1: ...User Manual Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter CTL UM 01026 EN 04 August 2014...

Page 2: ...Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page ii August 2014...

Page 3: ...rm C Relay COM N O and N C 9 Normally Open Solid Switch 11 Analog Outputs 11 RS 485 Communication Wiring 12 USB Communications Port 12 Programming 13 Programming Flow Charts Relays 13 Key Pad Display...

Page 4: ...Troubleshooting 26 Trouble Codes 26 Specifications 27 Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page iv August 2014...

Page 5: ...AC DC to the optional 120 240V AC Nonvolatile memory no battery backup is required Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes f...

Page 6: ...el Mount is designed for through panel mounting which allows access to the back of the unit The 3100 is secured to the panel by two draw brackets shown in Figure 2 below Wall Mount Badger Meter does n...

Page 7: ...he power supply to the Series 3100 terminal marked LV AC DC and connect the negative end of the power supply to the Series 3100 terminal marked LV AC DC Earth ground can be connected to the terminal m...

Page 8: ...ar panel terminals are used all parameters are set with the LCD keypad interface No internal or external jumpers switches or potentiometers require movement or adjustment Pulse Inputs Solid State Swit...

Page 9: ...our mechanical form C relays one solid state normally open N O switch closure two analog outputs RS 485 for Modbus and BACnet communications and a USB connector for configuration and other purposes Se...

Page 10: ...Figure 8 High flow shut down and normally open master valve Figure 9 High flow shut down with irrigation clock and normally closed master valve Installation Page 10 August 2014 CTL UM 001026 EN 04...

Page 11: ...o analog outputs Each is isolated and independent and can be configured for 0 20 mA or 4 20 mA This unique design permits external conversion to externally to 0 5V DC or 1 5V DC with a 250 ohm resisto...

Page 12: ...e 12 RS 485 communication wiring Modbus BACnet USB Communications Port Using the USB Port requires Windows HyperTerminal or other similar communications software Figure 13 USB port Installation Page 1...

Page 13: ...rogramming Flow Charts Relays The following block diagrams explain various programming areas and are organized as follows Figure 14 Model 3100 programming chart Programming Page 13 August 2014 CTL UM...

Page 14: ...Figure 15 Flow inputs Programming Page 14 August 2014 CTL UM 001026 EN 04...

Page 15: ...Figure 16 Relays pulse outputs Programming Page 15 August 2014 CTL UM 001026 EN 04...

Page 16: ...Figure 17 Analog inputs Programming Page 16 August 2014 CTL UM 001026 EN 04...

Page 17: ...Figure 18 RS 485 communication port Programming Page 17 August 2014 CTL UM 001026 EN 04...

Page 18: ...the MENU Button One each screen there are three Choices In this case RESET SETUP and DIAG selects RESET selects SETUP and selects DIAG RESET SETUP DIAG Main Set up screen accessed by press MENU One ea...

Page 19: ...u Enter Set point 1 00000000 Menu Enter Figure 19 Selection screen Option List Screens Units of measure is an example of an options list Press to scroll up the list and to scroll down through the list...

Page 20: ...her set point crossing before restarting the count from zero LATCH Locks relay in energized state If Latch is chosen once energized by the set point time delay the relay will remain energized until re...

Page 21: ...006 30007 4 Flow 2 Total Input Register 30008 30009 BACnet The Model 3100 can be configured to communicate on a BACnet RS 485 MSTP Master Slave Token Passing system Configuration is via the front pane...

Page 22: ...ata bits 1 stop bit no parity and no flow contr 6 When connected a symbol will appear in the upper left corner of the main HyperTerminal display screen 7 Press the Enter Key Both the Rx and Tx LED s o...

Page 23: ...ore amenable to scripting it still accepts the same commands Any command entered without an sign and variable will display the current setting Example Typing display line 1 returns 0 which is the vari...

Page 24: ...low rate min current flow 1 2 sensor avg 0 100 averaging time constant in seconds flow 1 2 rate units 0 19 flow channel rate units to display 0 GPM 1 gal s 2 gal hr 3 Mgal day 4 L s 5 LPM 6 L hr 7 ft3...

Page 25: ...1 5 rate x totalizer rate relay 1 5 ctime 0 10000 pulse width in milliseconds relay 1 4 latch on off turn on off relay latching relay 1 4 setpoint x relay 1 4 setpoint x relay 1 4 relpoint x relay 1...

Page 26: ...reading from analog input AD converter channel 1 32 Error reading from analog input AD converter channel 2 36 Error writing to analog input AD converter channel 1 37 Error writing to analog input AD...

Page 27: ...r sourcing Sinking 30V DS 0 mA max 3 V 20 mA min Sourcing 600 max load USB Communication Provides complete access to all programming and operation features Requirements USB 2 0 A to Mini B five pin ca...

Page 28: ...ico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa G...

Reviews: