Programming
Setting Up Outputs
Scaled Output
The scaled output allows you to send a pulse output for any eligible measured
value in the FC-5000 flow computer� To set up scaled output, first select an output
mode, then edit the parameters available for that output mode� The parameters
available depend on the selected mode�
The
Scaled Output
options are:
Option
Description
Ch 1 Output Mode
Selects the behavior of Output Channel 1�
Ch 1 Output
Parameter
Defines output characteristic of Output Channel 1�
Ch 2 Output Mode
Selects the behavior of Output Channel 2�
Ch 2 Output
Parameter
Defines output characteristic of Output Channel 2�
1� Navigate to
SYSTEM SETUP > ADVANCED SETUP > SCALED OUTPUT > CH1
OUTPUT MODE.
The
Output Mode
options are:
Option
Description
Output Off
Sends no output from the flow computer through the
output channel�
Pulse Output (Total)
Sends pulse(s)-per-total unit of measure�
Pulse Output (Rate)
Sends pulse(s)-per-rate unit of measure�
2� Highlight an output mode and press
ENTEO.
3� Press
BACKSPACE
to return to the
Scaled Output
menu�
4� Highlight
CH1 OUTPUT PAOAMETEO
and press
ENTEO
� The options vary,
depending on the mode (Total or Rate):
Option
Description
Output Source
Parameter assignment of the output
(such as flow or total)�
Pulse Full Scale
Maximum flow value of configured flow meter
(in units of measure)�
Pulse Low Scale
Minimum flow value of configured flow meter
(in units of measure)�
Pulse Max Frequency
Maximum frequency output value�
Page 31
July 2016
CTL-UM-01723-EN-01