PROGRAMMING
OTEE:
N
All of the following parameters appear in
Extended Programming
mode Parameters with an asterisk (*) appear in
Programming
mode as well
Parameters
Select Display Function
The ER-500 monitor has three display selections—
Flow
,
Grand Total
and
Test
Flow
Use the
Flow
setting for normal operation of the monitor In this mode, the display shows both the instantaneous flow rate
and current total simultaneously, see
2
1
Current Total Units
Flow Rate
Units
Totalizer
Multiplier
Current
Total
Instantaneous
Flow Rate
Figure 6: Instantaneous flow rate and current total
Flow Grand Total
The
Flow-GT
setting forces the meter to alternate between the instantaneous flow and the grand total with roll-over counts,
The grand total is the accumulation of all the fluid that has gone through the meter since the last time the grand total was
cleared This totalizer is in addition to the current total totalizer on the display and is always enabled
In addition, the grand total screen displays the number of times the grand total has reached its maximum count (9,999,999)
and rolled over to zero
2
1
Roll-over
Indicator
Totalizer
Mode
Total
Roll-Overs
Figure 7: Grand total
Test
The
Test
setting places the monitor into a special diagnostic mode that shows the current input frequency and the
accumulated input counts
shows the layout for test mode values The diagnostic mode makes it possible for you to
see precisely the frequency input the monitor is seeing and is very useful in troubleshooting and electrical noise detection
At the
Display
prompt, press
ENTER
to view the current display setting If the current display setting is correct, press
ENTER
to
advance to the next parameter To change the display setting, press
UP
or
RIGHT
to scroll through the display options Press
ENTER
to save and advance to the
KFacUnit
parameter
2
1
Input
Frequency
Totalizer
Counts
Figure 8: Test mode screen
Programming
DSY-PM-00028-EN-02
Page 16
February 2017
Summary of Contents for ER-500
Page 1: ...Display ER 500 Advanced DSY PM 00028 EN 02 February 2017 Programming Manual...
Page 2: ...ER 500 Flow Monitor Page ii February 2017 DSY PM 00028 EN 02...
Page 4: ...ER 500 Flow Monitor Page iv February 2017 DSY PM 00028 EN 02...
Page 34: ...Display ER 500 Advanced INTENTIONAL BLANK PAGE DSY PM 00028 EN 02 Page 34 February 2017...
Page 35: ...Programming Manual INTENTIONAL BLANK PAGE DSY PM 00028 EN 02 Page 35 February 2017...