TROUBLESHOOTING

Problem

Possible Causes

Remedies

Screen is blank

Battery is dead .

Replace battery .

Will not count in totalizer mode

1 .  Improperly programmed . 
2 .  Broken or defective wiring . 
3 .  Improperly connected .
4 .  Transmitter defective .

1 .  Check programming .
2 .  Check wiring .
3 .  Check connections .
4 .  Repair or replace transmitter .

Will not indicate rate of flow

1 .  Improperly programmed .
2 .  Improperly connected .
3 .  Transmitter defective .

1 .  Check programming .
2 .  Check connections .
3 .  Repair or replace transmitter .

Cannot program

Program-enable jumper is not installed or 

is installed improperly .

Install jumper from Terminal 1 to  

Terminal 5 .

Cannot reset from front panel

Reset enable is not programmed .

Reprogram mode to R  

(

Program Mode 6

) .

Erroneous readings

1 .  Improperly programmed .
2 .  Defective transmitter .

1 .  Check programming .
2 .  Repair or replace transmitter .

Table 4: Troubleshooting

For further assistance, call our Technical Support Staff at 1-800-876-3837 .

Troubleshooting

Page 12 

September 2017

REG-UM-00471-EN-07

Summary of Contents for ER-10

Page 1: ...Resettable Totalizer and Rate of Flow Indicator REG UM 00471 EN 07 September 2017 User Manual This product contains Lithium batteries Read this manual before attempting any installation wiring or ope...

Page 2: ...Industrial Registers Models ER 10 ER 10 R ER 10H Digital Resettable Totalizer and Rate of Flow Indicator Page ii September 2017 REG UM 00471 EN 07...

Page 3: ...rminals 7 Transmitter Connections 7 Operation 8 Display Types 8 Control Keys 8 Programming 9 Programming Calculations 10 Totalizer Programming 10 Rate of Flow Programming 10 Pulse Output Programming 1...

Page 4: ...Industrial Registers Models ER 10 ER 10 R ER 10H Digital Resettable Totalizer and Rate of Flow Indicator Page iv September 2017 REG UM 00471 EN 07...

Page 5: ...mer Service 1 800 876 3837 PRODUCT DESCRIPTION The ER 10 ER 10 R and ER 10H are external or battery powered electronic registers that display rate of flow and total flow They have independent programm...

Page 6: ...o meet NEMA 4X Mode select programming button Gasket installed Install mounting clip Figure 1 Panel installation Battery Installation Replacement The ER 10 ER 10 R ER 10H are powered by one 3V Lithium...

Page 7: ...bers in parenthesis refer to the terminal numbers on the ER 10 Connect the wire coming from the transmitter to the corresponding terminal number for the ER Series Remote models Connecting to a generic...

Page 8: ...Total Rate key during normal operation the ER 10 toggles the display between the Flow Total and the Flow Rate The letter R on the left of the screen indicates that the Flow Rate is being displayed Pro...

Page 9: ...ecimal point to the new position 3 0000 Mode 3 Rate Scale Factor display shows the lowercase letter d on the right when it is time to enter the decimal point position for the rate scaler NOTE N This d...

Page 10: ...ls hour Rate scale factor To determine the Rate Scale Factor Program Mode 4 use the following formula Rate Scale Factor Seconds Transmitter Pulses per Unit Decimal Factor where Seconds is the number o...

Page 11: ...0 52 396 1484 689 3 4 35 RCDL 126 671 33 463 947 566 1 40 RCDL 89 781 23 717 671 610 1 55 RCDL 58 064 15 339 434 351 1 70 RCDL 46 752 12 350 349 726 1 1 2 120 RCDL 23 867 6 305 178 539 2 170 RCDL 14 5...

Page 12: ...3 Transmitter defective 1 Check programming 2 Check connections 3 Repair or replace transmitter Cannot program Program enable jumper is not installed or is installed improperly Install jumper from Te...

Page 13: ...tank or into a calibrated vessel 5 Determine the number of pulses per gallon by dividing the indicator reading by the number of gallons of fluid in the vessel Use this value for your calculations Exam...

Page 14: ...the balance of the above steps to re assemble the unit Disc meter 1 Remove the front cover on the ER 10 unit and disconnect the sensor wiring 2 Loosen the side seal screw on the assembly adapter twist...

Page 15: ...rogrammable Rate Indicator Digits 4 5 4 calculated 5 displayed with fixed zero in LSD Scaler range 0 001 9999 Decimal point 5 positions programmable Accuracy 0 2 Update time 0 7 seconds Zero time 10 s...

Page 16: ...alupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur w Poland 48...

Reviews: