background image

5

The regeneration signal will be sent as soon as the lockout
signal is terminated. A lighted decimal point at the lower right
corner of the display will indicate the presence of a lockout
signal. (An open collector/switch contact or a 115 VAC signal
can be used as the lockout signal.) When using a 115VAC
lockout signal, the lockout logic can be reversed. (See settings
for Switch 2 in section below.) If the 115VAC lockout signal is
not used, Switch 2 must be in the off position. The lockout
signal will be ignored if the output is energized.

SELECTING THE MODE OF OPERATION

Select the mode of operation and maximum batch size re-
quired for your particular system. (For location of switches,
see page 7.)

Switch 1: ON

(

Manual 

operation)

OFF (

Automatic 

operation)

Switch 2: ON

(

Lockout 

when 115VAC

 

is not

 

applied

to TB-3)

OFF (

Lockout 

when 115VAC 

is 

applied to TB-3)

Note:  Switch 2 must be in the off position when not using 115
VAC lockout function.

Switches 3 & 4:  (See chart) Set switches for the maximum
batch size for your particular size of meter.

Example:  

You have a 2" Industrial Turbo meter and your batch

size is 500000 gallons, set switch 3 to the off position, and set
switch 4 to the off position. (This will allow you to set a maximum
batch size of 999000 gallons.) Attach the X1000 sticker to the
front panel.

Batch Capacity Selection Table

Zeros are not displayed.

Attach appropriate multiplier label to front panel.

Switch

Position

Max. Preset Value in US Gal.

for Meter Size (inches)

on

999

RCDL 25, 35,

40 & 70 (RTR)

Turbo Series

1 1/2" - 6" and

Ind. Turbo 6"

1 2 3 4

9990

99900

1 2 3 4

99900

9990

999000

1 2 3 4

99900

9990000

999000

1 2 3 4

99900000

999000

9990000

X1

X10

X100

X1000

X10

X1000

blank

X10

X1000

X10000

(no label)

X1000

X10000

X100000

(no label)

(no label)

RCDL 70 (AR/t),

120 & 170 and

Ind. Turbo 2", 3" & 4"

■   

OPERATION

The basic function of the AR/e controller
is to provide a signal to external equip-
ment once a predetermined amount of
water has been measured by the water
meter. The batch is preset and the dis-
play counts down to zero. At this point
the output relay is energized for a pro-

grammed period of time providing the necessary signal for
manual or automatic regeneration.

The controller is designed to function with a minimum of
operator control after the initial setup procedures. All displays
and controls are located on the front panel for fast, accurate
and convenient operation.

GENERAL PROGRAMMING PROCEDURE

In addition to the LED display and the digit keys, the front
panel of the AR/e controller has two command keys (START
and STOP) and three program keys (PRESET, SIGNAL DURA-
TION and UP-DOWN COUNT).

To prevent tampering or accidental mistakes, the keys must be
depressed twice in succession for the command to be recog-
nized and acted upon. 

If the second command is not received

within ten seconds of the first, the unit will revert back to its
previous operation.

PROGRAMMING SEQUENCE

To interrogate the present value

 of a programmable function,

depress the appropriate function key. The display will show
the function symbol and the present value of the function
alternately for ten seconds and then revert back to normal
operation.

To preset a new value

, press the appropriate key and change

the value by using the "

digits

" keys. Pressing a digit key

continuously will cause the number to scroll. When the desired
number is reached, remove your finger from the digit key.
Change one digit at a time, within ten seconds of each other.
After the new value is displayed, press the key again, to store
it in memory.

The unit will not react to any new values until it counts down
to zero. To accept the new values immediately, "zero" the unit
using the UP/DOWN key.

Summary of Contents for AR/e

Page 1: ...adgerMeter Inc Model AR e AR t RTR Service Information File manual for future reference and service Serial Number Date Installed Service Line Operator IMPORTANT Read this manual before attempting any...

Page 2: ...accessories for any physical damage such as scratches loose or broken parts or any other sign of damage that may have occurred during shipment Note If damage is found request an inspection by the carr...

Page 3: ...Note Terminalblockassemblyunplugsfromprintedcircuit board for ease in connecting field wiring Disconnect all power to the unit before connecting wires to any of the terminals Do not use machine power...

Page 4: ...re received IfaSTARTcommandisreceivedwhiletheLOCKOUTisactive the command will be stored in memory and acted upon as soon as the LOCKOUT signal is terminated Remote Stop Input Isusedtoterminatetheoutpu...

Page 5: ...0000 X100000 no label no label RCDL 70 AR t 120 170 and Ind Turbo 2 3 4 OPERATION The basic function of the AR e controller is to provide a signal to external equip ment once a predetermined amount of...

Page 6: ...se non rechargeable battery If you find it necessary to send unit to factory contact your Badger representative or dealer for material return authori zation Packagetheunitproperly andincludeabriefdesc...

Page 7: ...1 Defective relay 1 Replace relay See page 7 energized at end of batch or 2 Lockout is active 2 Check switch 2 position and wiring to when a START command is lockoutterminals received Signal indicator...