background image

7

PROBLEM

POSSIBLE CAUSES

REMEDIES

Display does not light when

1. No power on terminals 1 and 2.

1. Connect terminals 1 and 2 to power source.

AC power is turned on.

2. Blown fuse.

2. Replace fuse.

3. Shorted power wiring.

3. Remove short circuit.

Counter does not decrement

1. No flow through meter.

1. Establish flow through meter.

when transmitter is activated.

2. Defective transmitter.

2. Replace transmitter

3. Transmitter improperly connected.

3. Correct  wiring  error.

4. Dip switches improperly set.

4. Verify switch settings for your meter size.

Regeneration output is not

1. Defective relay.

1. Replace relay. (See page 7.)

energized at end of batch or

2. Lockout is active.

2. Check switch 2 position and wiring to

when a START command is

lockout terminals.

received. (Signal indicator is lit.)

Cannot change programmed

1. Function key is not being pressed

1. Refer to page 6 for proper programming

values.

twice.

sequence.

2. Unit not "zeroed" with UP/DOWN

2. Use UP/DOWN key to "zero" unit, which will

key.

force acceptance of new values.

Regeneration signal is active

1. Output is improperly wired.

1. Correct wiring errors.

when signal light is off.

2. Unit is defective.

2. Replace unit.

Test procedure does not work.

1. Unit is defective.

1. Replace unit.

Memory does not function

1. Battery is defective.

1. Replace battery.

during power outage.

AR/e Circuit Board

Summary of Contents for AR/e

Page 1: ...adgerMeter Inc Model AR e AR t RTR Service Information File manual for future reference and service Serial Number Date Installed Service Line Operator IMPORTANT Read this manual before attempting any...

Page 2: ...accessories for any physical damage such as scratches loose or broken parts or any other sign of damage that may have occurred during shipment Note If damage is found request an inspection by the carr...

Page 3: ...Note Terminalblockassemblyunplugsfromprintedcircuit board for ease in connecting field wiring Disconnect all power to the unit before connecting wires to any of the terminals Do not use machine power...

Page 4: ...re received IfaSTARTcommandisreceivedwhiletheLOCKOUTisactive the command will be stored in memory and acted upon as soon as the LOCKOUT signal is terminated Remote Stop Input Isusedtoterminatetheoutpu...

Page 5: ...0000 X100000 no label no label RCDL 70 AR t 120 170 and Ind Turbo 2 3 4 OPERATION The basic function of the AR e controller is to provide a signal to external equip ment once a predetermined amount of...

Page 6: ...se non rechargeable battery If you find it necessary to send unit to factory contact your Badger representative or dealer for material return authori zation Packagetheunitproperly andincludeabriefdesc...

Page 7: ...1 Defective relay 1 Replace relay See page 7 energized at end of batch or 2 Lockout is active 2 Check switch 2 position and wiring to when a START command is lockoutterminals received Signal indicator...

Page 8: ...pt to the extent an outstanding bid obligation exists BadgerMeter Inc P O Box 245036 Milwaukee WI 53224 9536 Telephone 414 355 0400 877 243 1010 Fax 414 355 7499 866 613 9305 www badgermeter com Copyr...

Reviews: