H-25C Instruction Manual
Instruction 3015-0216
12
1.3 SPECIFICATIONS
Specifications
Gas Measured:
Sensor:
Measurement Range:
Alarm Point Setting Range:
Measurement Modes:
Measurement Units:
Response Time:
Calibration:
Output Signal:
Contact Output:
Displays:
Audio Speaker:
Supply Voltage;
Power Consumption:
Dimensions:
Weight:
R134a or R12 gas
Cationic emission type sensor
9x10
-5
to 9x10
-4
std. ml/s, 1.5 to 150 g/yearly, 0.05 to 5.0 oz/yearly)
Note: One std. ml/s: Flow volume per second, converted to equivalent gas at 0° C 1 atm.
9x10
-6
to 9x10
-4
std. ml/s, 1.4 to 99 g/y, 0.05 to 5.0 oz/y
B-type measurement mode (for detecting leaks in a normal atmosphere
Auto zero mode: (for searching for leaks)
Auto zero hold mode: (for measuring leak flow)
A-type measurement mode (for detecting leaks in a clean atmosphere)
Search mode: (for searching for the location of leaks)
Pass/fail mode: (for measuring leak flow)
Either “x10
-5
std. ml/s” (x10-5 std. ml/s) or “g/y” can be selected
Approx. 1 second
Auto calibration (function supplied as option if specified)
Manual calibration (using “LS20B Leak Standard”)
0 to 1V DC, output resistance 1
Ω
max. (function supplied as option if specified
One “Alarm” point (output generated when measurement exceeds alarm setting) (function supplied as an option if
specified)
Relay state: Either an energized or de-energized state can be selected when the output is sent out.
Contact States: NO or NC, selectable
Contact rating: 2A (250 V AC, 30V DC)
Data display (3 digit numeric display)
Measured value, warm-up time countdown, cal request, idling operation, ect.
Bar graph indicator (0 to 200% in 20 segments)
Measured value, cal gas pressure – if equipped with auto cal function (indicated during warm-up and during
calibration), sensor sensitivity (at cal completion), etc.
Malfunction alarm display
“AIR FLOW” (measured gas intake flow), “CAL FAIL” (EE Prom failure, calibration gas pressure low, unable to
calibrate)
Type of gas display
Unit
Probe indicator (LED)
Indicates leak detection, cal request, cal operation in progress
Leak detection, cal request, cal operation in progress
100/115V AC, 50/60 Hz, 110/220 V AC, 50/60 Hz, or 120/240 V AC, 50/60 Hz
100VA
148 H x 210 W x 330 D mm, (5-13/16 H x 8¼ W x 13D in)
Approx. 10 kg (22lbs)