Troubleshooting 

Alarm conditions on the electronic controller, Call BCS Tech Services at 937-665-0424 
 
Unit will not reach temperature  

Call your installation contractor to Determine proper refrigerant 

 

 

 

 

 

charge.  Dirty condenser? 

Unit has shut off  

 

 

Call BSC tech services or field Service; could be bad Compressor, 

 

 

 

 

 

fans, controller or Pump 

 

Alarm Signaling 
Message 

 

 Cause  

 

 

 

Outputs 

“P1”    

 

Thermostat probe failure  

 

compressor and heating outputs off 

 

 

 

 

 

 

 

 

(on dehumidification system only) 

“P3”    

 

Humidity probe failure  

 

humidity regulation off 

“HA”    

 

High temp alarm  

 

 

outputs unchanged 

“LA”    

 

Low temperature alarm  

 

outputs unchanged 

“HHA”   

 

 High humidity alarm    

 

outputs unchanged 

“HLA”   

 

Low humidity alarm    

 

outputs unchanged 

In the instance of any of these alarms, call Bacchus Tech Services, or your local service contractor. 
 

Dimensional /Electrical 
 

 

 

 

BCS1000 

BCS1000 

BCS1500 

BCS1500 

BCS2000 

BCS3000 

 

 

Cond. Unit 

Evap. 

 

Con. Unit 

Evaporator 

Con. Unit 

Con. Unit 

 

 

Dims. 

  

17”D x 13.3”W      18”D x 29.25”W 

19”D x 16.2”W 

18”D x 29.25”W 

19”D x 21’W 

25” D x 20”W 

 

 

x 11.8”H   

x 6.5”H   

x 14”H 

 

x 6.5”H   

x 16.5”H   

x 16”H 

 

Weight    

51 lbs.    

49 lbs.    

62 lbs.    

51 lbs.    

81 lbs.    

135 lbs. 

 

Refrigerant 

3/8” suc.  

3/8”sw   

3/8” suc   

3/8” sw x 

3/8” suc   

½” suc 

Connection 

1/4” dis.   

 

 

¼” dis   

½” sw   

5/16” dis  

3/8” dis 

 

Water Supply 

 

 

¼” 

 

 

 

¼” 

Connection 

 

 

compression 

 

 

compression 

 

Condensate 

 

 

¼ mpt 

 

 

 

¼” mpt 

Connection 

 

Compressor 

1/2 hp 115v 

 

 

.65 hp 115v 

 

 

1 hp 115v 

1 ½  Hp 

HP/voltage 

 

 

 

 

 

 

 

 

 

 

208/230-1v 

 

Electrical 

 

compressor rla   10A  

 

 

 

11A  

 

 

 

8A  

 

12.1A 

 

compressor lra 

 53A  

 

 

 

51A  

 

 

 

43A  

 

49A 

 

cond. Unit MFS   20A  

 

 

 

30A  

 

 

 

15A  

 

17.6A 

 

cond. Unit mca   13.4A    

 

 

13.4A    

 

 

11.3A    

12.1A 

 

BTU capacity 40F  4857 

 

 

 

6250 

 

 

 

10200 (100 amb) 

12,185 

suc, 110 amb. 
 

Summary of Contents for BCS1000

Page 1: ...dependent upon your condensing unit for outdoor condensing unit Check local codes 5 18 2 stat wire to be used to extend temperature sensor humidity sensor cable keyboard 6 Condensing unit pad Condensing Unit Set Up 1 Place a suggested model on a firm level location pad for outdoor applications or add 4 anti vibration pads to each corner of the condensing unit for indoor use Place in an area with a...

Page 2: ...out to a suitable location Heat tape any portion susceptible to freezing 3 Attach template to the ceiling Remove the stainless steel outer enclosure from the base of the unit Attempt to locate any mounting holes below ceiling joists for secure attachment with 8 wood screws Use moly bolts for all other mounting locations Attach base securely to the ceiling diagram 1 Minimum 7 mounts 4 Bring in powe...

Page 3: ...r supply Shut off water supply to the line and braze in the CPS water supply compression adapter Connect the water filter to the fitting and run copper from the filter thru the evaporator ceiling opening and cap and attach to the water solenoid inlet in each evaporator 8 Attach the 1 4 vinyl hose drain tube to the outlet of the green condensate pump 9 For indoor applications run 1 4 vinyl condensa...

Page 4: ...xpose to water or moisture use the controller only Within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation 6 Warning disconnect all electrical connections before any kind of maintenance 7 Ensure that the wires for probes leads and the power supply are separated and are not intertwined or crossed XH10P Humidity Sensor 8 The...

Page 5: ... temperature alarm outputs unchanged HHA High humidity alarm outputs unchanged HLA Low humidity alarm outputs unchanged In the instance of any of these alarms call Bacchus Tech Services or your installation contractor Power to the Evaporator 1 Bring in 14 2 conductor wire with ground to the evaporator and connect to the 14 2 with ground wire harness exiting the evaporator Make sure the line has ad...

Page 6: ...nd replace the cover Power up the evaporator and let the system pull down At temp set point the refrigerant solenoid will close and the system will pump down and shut off the condensing unit 5 Check level of safety float Breakers We recommend a 30a fused disconnect Maintenance and Troubleshooting Have your system checked each year by a certified refrigeration technician He should 1 Clean the indoo...

Page 7: ...nchanged In the instance of any of these alarms call Bacchus Tech Services or your local service contractor Dimensional Electrical BCS1000 BCS1000 BCS1500 BCS1500 BCS2000 BCS3000 Cond Unit Evap Con Unit Evaporator Con Unit Con Unit Dims 17 D x 13 3 W 18 D x 29 25 W 19 D x 16 2 W 18 D x 29 25 W 19 D x 21 W 25 D x 20 W x 11 8 H x 6 5 H x 14 H x 6 5 H x 16 5 H x 16 H Weight 51 lbs 49 lbs 62 lbs 51 lb...

Page 8: ...8 Phone 937 665 0424 Fax 937 890 6664 ...

Reviews: