TrilliumSeries™ Adiabatic
Cooler - TRF Rigging & Assembly Instructions
–
Warnings and Cautions
Page | 5
Equipment Precautions
NOTICE
•
Before an actual lift is undertaken, open the access hatch(es) and check to ensure no water, snow, ice, or debris has
collected in the sump or elsewhere in the unit. Such accumulations will substantially add to the equipment’s lifting weight.
•
BAC units are typically installed immediately after shipment, and many operate year-round. However, if the unit is to be
stored for a prolonged period either before or after installation, certain precautions should be observed. Refer to Section
Prolonged Outdoor Storage for details.
•
Do not use steam, high-pressure water, or high-pressure air to clean any component.
•
Field piping must not be supported by the unit inlet or outlet connections.
•
The installer must ensure a proper air purging of the system prior to operation. Entrained air can restrict the capacity of
the cooler, resulting in higher process temperatures. All connections including those installed by others must be leak free
and tested accordingly.
•
To prevent possible contamination of the make-up water supply, install a backflow prevention method in accordance with
applicable local and national codes.
•
The pre-cooler pads are made of flammable material and should be removed when performing hot work on or near the
unit. No actions that can generate sparks should be performed on or near the unit.
•
To prevent excessive degradation do not attempt to remove the pre-cooler pads while wet.
•
When connecting power to the unit, do not penetrate the control panel. Doing so may allow moisture to enter the panel. All
cable and conduit should be supported separately from the unit. Do not penetrate the unit for supports or other
connections.