TrilliumSeries™ Adiabatic

 Cooler - TRF Rigging & Assembly Instructions 

 Rigging                                            

Page | 7

 

The following parts should be inspected (if applicable for the unit’s configuration):

 

 

Adiabatic pre-cooler pads 

 

Interior surfaces 

 

Control panel 

 

Sump components 

 

Coil surfaces 

 

Water connection piping 

 

EC fan module(s) 

 

Water distribution system 

 

Exterior surfaces 

 

 

Fan guard(s) 

 

 

Leaving fluid temperature sensor 

 

For TrilliumSeries

 adiabatic coolers that have been shipped charged with nitrogen, verify that the coil maintained pressure of 

15 psi (1 bar) by measuring the pressure with a pressure gauge on the Shrader valve prior to installation. The leaving fluid 
temperature sensor is shipped loose and stored inside the electrical cabinet for installation on site. 

 

Unit Weights

 

Before rigging any unit, the weight of each section should be verified with the unit submittal drawing.

 

In the event of extended 

lifts or where hazards exist, the lifting devices should be used in conjunction with safety slings placed under the unit. 
 

 

NOTICE: 

Before an actual lift is undertaken, open the access hatch and check to ensure no 

water, snow, ice, or debris has collected in the sump or elsewhere in the unit. Such 
accumulations will substantially 

add to the equipment’s lifting

 weight. 

 

Anchoring 

7/8”

 diameter holes are provided in the bottom flanges of the unit for bolting the unit to the support beams. Refer to the 

suggested support drawing included in the submittal for location and quantity of the mounting holes. 

The unit must be level 

within 1/16”

 per foot in both length and width directions for proper operation. 

Supporting steelwork and anchor bolts are 

to be designed and furnished by others. 

BAC recommends 3/4” 

diameter, SAE J429 Grade 5, ASTM A325 Type 1 or 

equivalent anchor bolts. Beams should be selected in accordance with accepted structural practices. Supporting steel must be 
greater than or equal to the length 

of the unit’s base

, and the unit may not be point supported. Each beam should be designed, 

as a minimum, for 65% of the total unit operating weight applied as a uniformly distributed load. If vibration isolators are to be 
used, the units shall be installed on steel support first and the vibration isolators (provided by others) should be mounted under 
the steel support. Refer to the vibration isolator 

manufacturer’s guidelines before loading/unloading weight

 from the unit. When 

a unit is anchored directly to concrete on grade without steel supports, the support concrete must be flush and level at top. 
Concrete for unit support and anchors are to be designed and furnished by others in accordance with accepted structural 
practices. When units are anchored by anchor rods, 

3/4”

 diameter ASTM F1554 Gr. 105 anchor rods or equivalent are 

generally recommended. 
 

 

WARNING: 

To prevent severe injury, death and/or property damage

 

the unit must be properly 

anchored before operation begins. 

 
 
 

Summary of Contents for TrilliumSeries TRF-1010N-C80GX17E

Page 1: ...TrilliumSeries Adiabatic Cooler TRF RIGGING ASSEMBLY INSTRUCTIONS...

Page 2: ...ed to do so should undertake the installation operation maintenance and repair of this equipment Proper care procedures and tools must be used in handling lifting installing operating maintaining and...

Page 3: ...7 Layout Guidelines 8 Warranties 8 Rigging 9 Prolonged Outdoor Storage 9 Storage Preparation 9 Motor Recommendations 10 Preparation After Prolonged Storage 10 3 Installation 11 Piping Guidelines 11 Wa...

Page 4: ...d load causing severe injury death and or property damage Lifts must be performed by qualified riggers following BAC published Rigging Instructions and generally accepted lifting practices The use of...

Page 5: ...t or outlet connections The installer must ensure a proper air purging of the system prior to operation Entrained air can restrict the capacity of the cooler resulting in higher process temperatures A...

Page 6: ...es adiabatic coolers are factory assembled to ensure uniform quality with minimum field assembly For each unit only one lift is required Contact your local BAC Representative for more information For...

Page 7: ...the unit to the support beams Refer to the suggested support drawing included in the submittal for location and quantity of the mounting holes The unit must be level within 1 16 per foot in both leng...

Page 8: ...kage applicable to and in effect at the time of the sale purchase of these products Rigging Summary 1 The equipment arrives on site by truck A crane must always be used to unload the unit from the tru...

Page 9: ...the storage recommendations below NOTICE BAC units are typically installed immediately after shipment and many operate year round However if the unit is to be stored for a prolonged period of time ei...

Page 10: ...the motor from flooding or from harmful chemical vapors The storage area should be free from ambient vibration Excessive vibration can cause damage Keep stored motor s dry and protected from weather...

Page 11: ...restrict the capacity of the cooler resulting in higher process temperatures All connections including those installed by others must be leak free and tested accordingly Water Connection Refer to Fig...

Page 12: ...show the dimensions of the socket The socket is equipped with a PG7 IP68 cable gland applied to the hexagonal end to secure the cable The socket and sensor need to be installed in accordance with the...

Page 13: ...Electrical Information Electrical Power Quality This unit requires clean electrical power to operate properly Voltage and frequency should be within 10 of the designed voltage for the unit Failure to...

Page 14: ...s via Modbus RS485 BACnet MS TP or BACnet IP For RS485 connection BAC recommends the use of twisted shielded twisted paired wire with a ground The Modbus and BACnet connections do not have any device...

Page 15: ...TrilliumSeries Adiabatic Cooler TRF Rigging Assembly Instructions Rigging Drawings Page 15 4 Rigging Drawings This page intentionally left blank...

Page 16: ...intenance 4 FAN RIGGING 8 M E T E R S 2 6 F E E T MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 2684 mm 105 1 2 in 2908 mm 114 1 2 in 1353 mm 531 2 in 1451 mm 57 in 1458 mm 571 2 in NOTES...

Page 17: ...aintenance 6 FAN RIGGING 8 M E T E R S 2 6 F E E T MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 4020 mm 158 1 2 in 2908 mm 114 1 2 in 1995 mm 78 1 2 in 2183 mm 86 in 1411 mm 55 1 2 in 14...

Page 18: ...Maintenance 8 FAN RIGGING 8 M E T E R S 2 6 F E E T MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 5220 mm 205 1 2 in 2908 mm 114 1 2 in 2664 mm 105 in 2714 mm 107 in 1454 mm 57 1 2 in 145...

Page 19: ...Maintenance 10 FAN RIGGING 8 M E T E R S 2 6 F E E T 6420 mm 253 in 2908 mm 114 1 2 in MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 3270 mm 128 1 2 in 3308 mm 130 in 1454 mm 57 in 1455 m...

Page 20: ...Maintenance 12 FAN RIGGING 8 M E T E R S 2 6 F E E T MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 6420 mm 253 in 2908 mm 114 1 2 in 3941 mm 155 in 3948 mm 155 1 2 in 1454 mm 57 in 1454 m...

Page 21: ...intenance 14 FAN RIGGING 8 M E T E R S 2 6 F E E T MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 6420 mm 253 in 2908 mm 114 1 2 in 4590 mm 180 1 2 in 4612 mm 181 1 2 in 1454 mm 57 in 1454...

Page 22: ...Maintenance 16 FAN RIGGING 8 M E T E R S 2 6 F E E T MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 6420 mm 253 in 2908 mm 114 1 2 in 5171 mm 203 1 2 in 5230 mm 206 in 1454 mm 57 in 1454 m...

Page 23: ...tenance 18 FAN RIGGING 8 M E T E R S 2 6 F E E T 6420 mm 253 in 2908 mm 114 1 2 in MAXIMAL DEVIATION IS 28INCH 0 7M FROM THE SIDE OF THE UNIT 5777 mm 227 1 2 in 5825 mm 229 1 2 in NOTES Please note th...

Page 24: ...TrilliumSeries Adiabatic Cooler TRF RIGGING ASSEMBLY INSTRUCTIONS baltimoreaircoil com 2022 Baltimore Aircoil Company 7600 Dorsey Run Road Jessup MD 20794 410 799 6200 RGRATRF01_R1 0...

Reviews: