LEGEND
Q
0
Main Power Switch
FINV
Inverter's Fuses
FA
1
Auxiliary Fuses - Transformer T
1
FA
2
Auxiliary Fuses - 230 V supply
FA
3
Auxiliary Fuses - 24 V supply
T
1
Transformer 400/ 0 – 230 - 24 V
F
1
, F
2
, F
3
, etc.
Circuit Breakers
DVW
Pad Maintenance Switch
DINV
Control Operation Switch
TH
Electrical Panel Ventilation Thermostat
MF
Electrical Panel Ventilator
Q
1
, Q
2
, Q
3
etc.
Thermal Overload Relay
K
1
, K
2
, K
3
etc.
Fan Contactor Relay
INV
Inverter
VH
1
City Water Solenoid Valve
VD
1
Drain Solenoid Valve
QAC
Ambient Air Sensor
QAE
Fluid Temperature Sensor
S
0
Emergency Stop Switch
S
01
Power Failure Reset
C
01
Power Failure Relay
H
0
Indicating Lamp
QBO
Power Invertor By-pass Switch (optional)
F
0
Main Fuses (with optional Inverter By-pass Switch)
Legend for Electrical Panel with Variable Frequency Drive
START-UP
1. Turn the main power switch Q0, main fuses FINV and auxiliary control circuit fuses FA1, FA2, FA3 to the “off”
position. Put the Circuit Breakers F1, F2, F3 etc. in the “off” position. Measure the mains voltage.
2. Turn the main power switch Q0 and FINV "on" and push Power Failure Reset Button S01 to power the inverter;
its LCP (Local Control Panel) is energised. Place the main fuses FA1, FA2, FA3, to the "on" position. The
amber indicating lamp on the front panel lights up. Put the Circuit Breakers F1, F2, F3 etc. in the “on” position.
W W W . B A L T I M O R E A I R C O I L . C O . Z A
18
Summary of Contents for SP2B series
Page 1: ...SP Adiabatic Cooler RIGGING AND INSTALLATION INSTRUCTIONS RSPv07EN SA...
Page 11: ...All 6 fan units W W W B A L T I M O R E A I R C O I L C O Z A 11 2 Rigging 2 Rigging...
Page 21: ...W W W B A L T I M O R E A I R C O I L C O Z A...
Page 22: ...W W W B A L T I M O R E A I R C O I L C O Z A...
Page 23: ...W W W B A L T I M O R E A I R C O I L C O Z A...
Page 24: ...W W W B A L T I M O R E A I R C O I L C O Z A...
Page 25: ...W W W B A L T I M O R E A I R C O I L C O Z A...