R3 - Timer dosing of biocide
HOA Setting
Auto
Event 1
Repetition: 1 week
Day: Monday
Start time: 8:00:00
Duration: 0:15:00
Event 2
Repetition: 1 week
Day: Wednesday
Start time: 8:00:00
Duration: 0:15:00
Event 3
Repetition: 1 week
Day: Friday
Start time: 8:00:00
Duration: 0:15:00
Event 4...10
Inactive
Bleed
Bleed (R1)
Prebleed time
0:00:00
Prebleed to
1150 µS/cm
Cond Input
Conduct (S1)
Bleed lockout
1:00:00
Interlock channels
D1
Activate with channels
None
Min Relay Cycle
0 sec
Hand time limit
0:10:00
Name (change with language - default is English)
Bio Timer
Mode
Biocide Timer
W W W . B A L T I M O R E A I R C O I L . E U
19
5 Controller Settings
5 Controller Settings