CONTROLLER SETTINGS
Default parameters and set points
The BACT 100 controller has been preprogrammed specifically for use with BAC evaporative cooling
equipment.
MENU INPUT
S1 - Conductivity
LoLo Alarm (Very low alarm)
200 µS/cm
Low Alarm
200 µS/cm
High Alarm
3500 µS/cm
HiHi Alarm (Very high alarm)
3500 µS/cm
Deadband
25 µS/cm
Alarm suppression
none
Reset Calibration values
Cal Req'd Alarm
365 days
Smoothing factor
0 %
Cell Const
1,000 1/cm
Cable length
6,10 m
Gauge
22 awg/0,35mm²
Default temp
25 °C
Temp Comp
NaCl
Units
µS/cm
Name (change with language, default is English)
Conduct
Type
Contacting Cond
16
BCP2D
5
5 Controller Settings