5 Test Procedure
32
DHV0053 b2 EN
©
b2electronic
gmbh
MR5: Test Start up
“Startup” appears on the screen to indicate
that the HVA is initializing the test
MR6: Set Test Voltage
(if not preset in step MS 8)
Rotate navigation knob (5) to modify the
voltage value.
•
Min. test voltage = 0.0kV
•
Max. voltage = 20.0kV rms (VLF), 28.0kV
(DC)
MR7: Test
Test begins automatically
The bottom of the screen indicates the lapsed
time
T: lapsed time / total test duration
MR8: Test End
Display indicates end of Manual Test
Summary of Contents for HVA28TD
Page 1: ......
Page 2: ......
Page 4: ...1 Forward 2 DHV0053 b2 EN b2electronic gmbh ...
Page 73: ......