WIRING DIAGRAM

1.  Pull branch circuit wiring. Make watertight 

connections from primary branch circuit 

to in-use receptacle using waterproof wire 

connectors. Connect incoming ground  and 

ground from receptacle to ground wire on 

base.

 See wiring diagram.

INSTALLATION OF IN-USE RECEPTACLE (RE1 & RE2 Option)

2.  Attach ground from branch circuit to screw 

on anchor base. Place connectors inside 

receptacle. 

3.  Attach in-use receptacle to installed anchor 

base with four (4) #10-32 button head stainless 

steel cap screws at the base using a 1/8” allen 

wrench.

4.  Receptacle cover has captive #6-32 screw. 

Secure receptacle by tightening captive #6-32 

set screw using a 7/64” allen wrench. 

Receptacle cover has two (2) openings for 

in-use cord sets. 

7.  Mount base and plate to concrete using 

mounting holes drilled previously (Mounting 

Hardware by Others). Minimum 1/4” diameter 

sleeve or wedge anchors for concrete must be 

used.

9.  Seal base and plate as per NEC. Continue with 

installation of In-Use Receptacle option chosen.

8.  Tighten four (4) #10-32 screws in base using a 

3/32” allen wrench to secure to installed PVC 

housing.

IMPORTANT SAFETY INFORMATION LISTED ON REVERSE

READ, FOLLOW, AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS

Receptacle Bollard

Installation Instructions