background image

Auto - backlit is turned on for 30 secs when any key is pressed.

Liquid Crystal Display

In  normal  operating  mode,  the  upper  LCD  displays  the  current  sensor 
temperature and the lower LCD displays the setpoint temperature. The display is 
also  used  with  the 

Up 

and 

Down 

key 

to  adjust  the  setpoint  temperature, 

differential and heating/cooling modes of the operation.

LCD Blue Backlit Options:

 set by slide switch on the front panel

ON - backlit is turned on.
OFF - backlit is turned off.

The  base  has  standard  7/8”  (22mm)  knockouts  which  accept  common  wiring 
hardware and conduit fittings. Before removing the knockouts, check the wiring 
diagrams and use the chamber with common voltages. 

ROUGH-IN WIRING

Loosen the screws on the top and bottom of the enclosure and remove the wiring 
covers by swinging them away from the base(grey color) with the edges of the 
covers as pivot(see Figure 1). 

Figure 1

Side view

Heating Mode and Cooling Mode: 

set by keypad

The control output will turn on when the sensor temperature falls to the setpoint 
temperature minus the differential amount. The control output will turn off when the 
sensor temperature reaches the setpoint temperature. For example, if setpoint = 
68F, Differential = 3F, then output is on at 65F and off at 68F. In other words, when the 
heating  mode  is  chosen,  the  differential  is  below  the  setpoint. The  relay  will  de-
energize as the temperature rises to the setpoint. Refer to Figure 2. 

The control output will turn on when the sensor temperature rises to the setpoint 
temperature plus the differential amount. The control output will turn off when the 
sensor temperature reaches the setpoint temperature. For example, if setpoint = 
75F, Differential = 2F, then output is on at 77F and off at 75F. In other words, when 
cooling  mode  is  chosen,  the  differential  is  above  the  setpoint. The  relay  will  de-
energize as the temperature falls to the setpoint.

Heating Mode 

(factory setting): 

From the isolated SPDT relay output, “NO” are normally open contacts which close 
and “NC” are normally closed contacts which open when the control output is on. 

Cooling Mode

 : 

The control output turned on means: 

 
RED light indicates that the SPDT relay output is energized.

L.E.D. SYSTEM STATUS INDICATION LIGHTS:

The single stage models (DST-777S, DST-777D) offer optimum control by 
means of a Pulse Width Modulation(PWM). In PWM, the ON and OFF cycle 
vary  depending  on  the  difference  between  the  sensor  and  setpoint 
temperature.  The  bigger  difference  between  the  sensor  and  setpoint 
temperature,  the  longer  the  relay  is  switched  ON.  When  the  sensor 
temperature  approaches  the  setpoint  temperature,  the  ON  time  become 
shorter  and  shorter.  Pulse  Width  Modulation  guarantees  precise  control 
response. This  function  prevents  overshoots  and  undershoots  in  systems 
with large thermal mass (eg. slabs or pools).

Figure 3 shows the operation of relay on Heating Mode during PWM cycle:

!

If  the  sensor  temperature  is  half  of  the  PWM  Differential  below  the 
setpoint temperature (in this example is: 71 F (75 - 8/2), relay is ON. 

°

!

°

°

If the sensor temperature is between 71 F  and 79 F , PWM is in action. 
When the sensor temperature crosses the rising slope of the triangle 
wave generated by the control, relay is turned ON during the shaded 
region.  When  the  sensor  temperature  passes  the  falling  slope  of  the 
triangle wave, the relay is turned OFF during the unshaded region.

!

The pulse width (the relay ON time within one cycle) is modulated in 
according to how far the sensor temperature deviates from the setpoint 
temperature.

!

If  the  sensor  temperature  is  half  of  the  PWM  Differential  above  the 
setpoint temperature (in this example is: 79°

F (75 + 8/2), relay is OFF. 

!

If sensor temperature is the same as the setpoint temperature, the pulse 
width is half (50%) of the cycle length.

!

If the sensor temperature is higher than the setpoint temperature, the 
pulse width allows shorter period of ON time

Pulse Width Modulation (PWM) 

Mode(PWM CONTROL): Set PWM slide 

switch to ON

!

If PWM mode is selected, the minimum time delay is disabled. 

!

If the sensor temperature is lower than the setpoint temperature, the 
pulse width allows longer period of ON time.

!

The principle of operation on Cooling Mode is the same with the shaded 
and white area reversed in Figure 3.

Setpoint
= 75 F 

°

Time

Sensor Temperature Curve

PWM Cycle Length

PWM Differential
= 8 F

°

Grey Area = ON region

White Area = OFF region

Relay Turned Off

Relay turned On

Figure 3: Operation of relay on heat mode during Pulse Width Modulation(PWM) cycle

71 F 

°

Temperature

79 F 

°

(Pulse width)

ON (relay energized)

Setpoint

OFF

(relay de-energized)

ON

OFF

Temperature

+

-

Heating

Mode

Cooling

Mode

Figure 2: Operation of relay in according to Setpoint and Differential 

Settings for both Heating and Cooling Mode

Normal Control Mode(ON/OFF Control): 

Set PWM slide switch to OFF

The control outputs will turn on the equipment when there is a demand for 
heating or cooling. When the demand is satisfied, the control outputs will turn 
it off. 

 

OPERATION

Anti-Short Cycle Delay can be set to ensure the output relay remains off for up 
to 20 minutes (default is 0 mins) after relay is de-energized. This is adjustable 
from  0  to  20  min  with  1  minute  increments.  In  other  words,  this  function 
establishes  the  minimum  time  that  the  output  relay  remains  de-energized 
before the next on-cycle. It does not allow the output relay to re-energize until 
the programmed time delay has elapsed. The delay is activated when the 
control is first turned on, but can be skipped during the display of “1SP.S” at 
startup by pressing the “SET” key once and go to normal operating mode 
(Note:  SET  key  at  this  stage  will  not  perform  any  other  function  except 
terminating the time delay).

 Anti-Short Cycle Delay  is available only when 

PWM is off .

Anti-Short Cycle Delay: 

set by keypad

When the delay is activated, the Upper LCD shows the current temperature 
and the lower LCD shows  blinking “AC” which stands for Anti-Cycle. Also, in 
case there is a demand for heating/cooling, the red LED for relay output will be 
blinking indicating that anti-cycle feature prevents relay from energizing.

Summary of Contents for DST-777S

Page 1: ...uch as pools or slabs A sensor probe P 01 is supplied with the control This solid state temperature sensor probe can be extended up to 500 feet APPLICATION DST 777 series controls are microprocessor based electronic one or two stage setpoint temperature controls designed to provide one or two on off controls Single Pole Double Throw SPDT relay outputs for residential commercial heating cooling air...

Page 2: ...fferential below the setpoint temperature in this example is 71 F 75 8 2 relay is ON If the sensor temperature is between 71 F and 79 F PWM is in action When the sensor temperature crosses the rising slope of the triangle wave generated by the control relay is turned ON during the shaded region When the sensor temperature passes the falling slope of the triangle wave the relay is turned OFF during...

Page 3: ...e delay blinking in minute and the upper LCD will display AC1 Then press either the Up key to increase or the Down key to decrease the delay to the desired setting The increment is in 1 minute Press SET key again to go back to normal operating mode The default value is F Description Anti Short Cycle time delay Differential Temperature Cooling or Heating Fahrenheit or Celsius Scale Default setting ...

Page 4: ...n for another three seconds to unlock the keypad The word Lof appears on the screen for 3 seconds which indicates that the keypad is enabled Factory setting unlock Review Setting Mode Press both Up and Down keys at the same time to review the current control settings Then Press or Up key to scroll through the settings in the Down same order as Program Mode F C scale Setpoint Differential Heating C...

Reviews: