Press and hold the 

Up 

Key or 

Down 

Key to change the value continuously (auto repeat function). 

General Note:

!

During the program mode, each time 

SET 

key is pressed, the data will be saved into the EEPROM and advance to the next setting(parameter). If no change of 

value is required, just press 

SET 

key once to go to the next step (parameter).

Quickset allows the user to change the setpoint temperature instantly without entering the program mode.   Simply press 

UP 

(increase) or 

Down 

(decrease) key 

during the normal operating mode. When the 

Up/Down

 key is pressed, the setpoint is flashing to indicate that the setpoint value can be changed. Press the 

UP/Down 

k

ey again to adjust the setpoint (press and hold for auto repeat function). Press 

SET 

key when finish or just walk away and it will return to normal mode after 30 

seconds. 

!

To return to normal operating mode from the program mode, press and hold the 

SET 

key for 3 seconds. However, the system also return to normal operating 

mode if no key is pressed for 30 seconds.

QuickSet  Feature:

SETTING THE CONTROLS

Program Mode:

Steps

Step1

 

Step 2

Step 4

Step 5

Step 3

Procedures

To  start  programming,  press  the 

SET 

key  for  3  seconds  to  access  the 

Fahrenheit/Celsius mode. The lower LCD display will show the current status, 
either 

F

 for degrees Fahrenheit or 

C

 for degrees Celsius. This annunciator will be 

flashing. Then press either 

Up

 or 

Down 

key to toggle between the 

F

 or 

C

 scales.

** Please note that this value as well as all the temperature related value are           

in degree Fahrenheit as set in step 1. 

Press 

SET

 key again to access the differential mode. The lower LCD will display 

the current differential (blinking) and the upper LCD will display 

dF1

 annunciator. 

Then  press  either  the 

Up 

key  to  increase  or  the 

Down 

key  to  decrease  the 

differential to the desired setting.

Press 

SET

 key again to access the heating or cooling mode. The upper LCD will 

display the current mode, with flashing annunciator, either 

H1

 for heating or 

C1

 

for cooling. Then press either the 

Up 

key or the 

Down 

key to toggle between the 

C1

 or 

H1

 operation.

Press 

SET

 key again to access the setpoint mode. The lower LCD will display the 

current setpoint (flashing) and the upper LCD will display 

S1 

annunciator. Then 

press either the 

Up 

key to increase or the 

Down 

key to decrease the setpoint to 

the desired setting.

Press 

SET

 key again to access the Anti-Short Cycle time delay. The lower LCD 

will display the current time delay(blinking), in minute and the upper LCD will 
display 

AC1

.  Then  press  either  the 

Up 

key  to  increase  or  the 

Down 

key  to 

decrease the delay to the desired setting. The increment is in 1 minute. Press 

SET 

key again to go back to normal operating mode.

The default value is 

F

Description

Anti-Short Cycle time delay

Differential Temperature 

Cooling or Heating 

Fahrenheit or Celsius Scale

Default setting is: 

75F

Setpoint Temperature

Default setting is: 

1F

Default setting is: 

H1

Default is: minutes

0

 

LCD Display

0

75

f

S i

8f i

   I

 

f

H i

Ac i

           

                                                                                                                 

 

S1 S1

    

      PWM

      ON

      OFF

240V  COM  120V

RELAY 1

NO C NC

SENSOR INPUTS

AC INPUT

93

Down Key

Up Key

Reset Key

Backlit Switch

Setpoint 

Temperature

Sensor 

Temperature

Fuse

Relay Output 

Status

Indicator LED

SET Key

PWM Switch

       120 VAC
          (HOT)

(COM)

LOAD

SENSOR 

PROBE

(P-01)

Figure 5: Typical Wiring Diagram for DST-777D

with 120Vac Loads

WIRING THE CONTROL

Refer to Figure 4 for 
typical wiring connections 
for DST-777S and Figure 
5 for DST-777D . Do not 
use wire larger than 12 
AWG as jumper between 
terminal blocks (eg. 
“120V” and “C”) 

Note: Set PWM slide switch to OFF

Programming Steps for Normal Control  Mode (ON/OFF Control)

All the slide switches (Backlit and PWM) should be set before the control is powered up (so the desired switch settings are scanned by the microprocessor). 
However if the settings on the slide switches are changed after power is supplied, press the 

RESET 

key so that the switch settings can be updated. 

POWER ON

When the control is powered up, the model ID - “1SP.S” or “1SP.d”   is displayed. Then the control will run Anti-short cycle delay(if any) and goes into normal 
operating mode in which the Upper LCD will display the current sensor temperature and the Lower LCD will display the setpoint temperature.

Figure 4: Typical Wiring Diagram for DST-777S 

with 120Vac Load

Terminal Representations: 

240V  is the hot of the 240Vac line voltage
COM is the neutral or ground of the line voltage

SENSOR INPUT

NC is Normally Close of SPDT switch and opens 
when the relay is energized

120V is the hot of the 120Vac line voltage

C is Common of the SPDT switch

S1 S1 are the input terminals for sensor probe P-01

NO is Normally Open of the SPDT switch and closes 
when the relay is energized

RELAY 1/RELAY 2

           

                                                                                                                 

 

S1 S1

    

      PWM

      ON

      OFF

240V  COM  120V

RELAY 1

NO C NC

SENSOR INPUTS

AC INPUT

       120 VAC
          (HOT)

(COM)

LOAD

SENSOR 

PROBE

(P-01)

RELAY 2

NO C NC

LOAD

!

Before power is applied to the 

control, make sure that the 
installation and wiring 
connections are done correctly. 
Also, ensure that the wires 
connecting to COM and 120V 
are not touching each other.

Checkout

!

Ensure that wires of the senor 

probe are not touching each 
other

Summary of Contents for DST-777S

Page 1: ...uch as pools or slabs A sensor probe P 01 is supplied with the control This solid state temperature sensor probe can be extended up to 500 feet APPLICATION DST 777 series controls are microprocessor based electronic one or two stage setpoint temperature controls designed to provide one or two on off controls Single Pole Double Throw SPDT relay outputs for residential commercial heating cooling air...

Page 2: ...fferential below the setpoint temperature in this example is 71 F 75 8 2 relay is ON If the sensor temperature is between 71 F and 79 F PWM is in action When the sensor temperature crosses the rising slope of the triangle wave generated by the control relay is turned ON during the shaded region When the sensor temperature passes the falling slope of the triangle wave the relay is turned OFF during...

Page 3: ...e delay blinking in minute and the upper LCD will display AC1 Then press either the Up key to increase or the Down key to decrease the delay to the desired setting The increment is in 1 minute Press SET key again to go back to normal operating mode The default value is F Description Anti Short Cycle time delay Differential Temperature Cooling or Heating Fahrenheit or Celsius Scale Default setting ...

Page 4: ...n for another three seconds to unlock the keypad The word Lof appears on the screen for 3 seconds which indicates that the keypad is enabled Factory setting unlock Review Setting Mode Press both Up and Down keys at the same time to review the current control settings Then Press or Up key to scroll through the settings in the Down same order as Program Mode F C scale Setpoint Differential Heating C...

Reviews: