Chapter 5. ADVANCED OPERATION
*8 If “5,” “6,” or “8” (operation mode switching) is selected for one of the external contact input func-
tion assignments (
C-
10
to
C-
12
) and if the valve is set to fully closed or fully open mode by
external contacts, the operation mode cannot be switched using the [RUN] key.
If the valve is set to control mode by external contacts, the operation mode can be switched
using the [RUN] key.
Based on the settings for
C-
10
to
C-
12
, the operation mode changes in accordance with the
input status as shown in the table below.
C-
10
to
C-
12
settings
Status of external contact input
ON
OFF
5
Fully closed mode
Control mode
Operation mode can be switched between control
/ fully closed / fully open using the [RUN] key.
6
Fully open mode
Control mode
Operation mode can be switched between control
/ fully closed / fully open using the [RUN] key.
8
Control mode
Operation mode can be switched be-
tween control / fully closed / fully open
using the [RUN] key.
Fully open mode
Handling Precautions
•
When the operational differential pressure setting (
C-36
) is changed
to "0: Low differential pressure (50 ± 50 kPa)," always use the device
with an operational differential pressure less than 100 kPa. Failure to
do so may cause overshoot or hunting of the flow rate.