![Azbil Micro Flow MQV0005 User Manual Download Page 30](http://html1.mh-extra.com/html/azbil/micro-flow-mqv0005/micro-flow-mqv0005_user-manual_3042629030.webp)
3-10
Chapter 3. MOUNTING AND WIRING
•
Alarm output/event output
12
11
10
9
+
-
Load
Load
Load
EV2 OUT
EV1 OUT
ALM OUT
or 6 D.GND
Handling Precautions
•
Take special care that the event and alarm outputs do not
exceed the output rating of the device. Additionally, when
driving a relay, use an appropriate coil surge absorption
diode built-in relay. Failure to do so might cause the device to
malfunction.
•
External contact input
15
14
13
9
DI3
DI2
DI1
or 6 D.GND
Handling Precautions
•
When switching by relay contact, use an appropriate relay
intended for micro-current use (with gold contacts). Failure to
do so could cause faulty contact, resulting in malfunction.
•
Analog I/O
19
18
17
+
—
+
—
0 to 5 V/1 to 5 V
0 to 20 mA/4 to 20 mA
0 to 5 V/1 to 5 V
0 to 20 mA/4 to 20 mA
FLOW OUT
A.GND
FLOW SP INPUT
Input
Output
•
When using potentiometer (0 to 5 V)
20
18
17
+5 V
A.GND (0 V)
FLOW SP INPUT