16
■
Alarm display
If conditions exceed the device's specified range, an alarm message and the instan-
taneous value are alternately displayed. In order to use this device within an allow-
able range, change the conditions of the fluid.
Flowrate upper limit alarm:
Flowrate speed 45m/s or more.
Temperature lower limit alarm:
-15
˚
C or lower.
Temperature upper limit alarm:
60
˚
C or more.
Pressure lower limit alarm:
-50kPa or lower.
Pressure upper limit alarm:
1000kPa or more.
Chapter 4. TROUBLESHOOTING
Alarm
Cause
display
AL01
Flowrate upper limit alarm
AL02
Temperature lower limit alarm
AL03
Flowrate upper limit alarm+Temperature lower limit alarm
AL04
Temperature upper limit alarm
AL05
Flowrate upper limit alarm+Temperature upper limit alarm
AL08
Pressure upper limit alarm
AL09
Flowrate upper limit alarm+Pressure lower limit alarm
AL10
Temperature lower limit alarm+Pressure lower limit alarm
AL11
Flowrate upper limit alarm+Temperature lower limit alarm+Pressure
lower limit alarm
AL12
Temperature upper limit alarm+Pressure lower limit alarm
AL13
Flowrate upper limit alarm+Temperature upper limit alarm+Pressure
lower limit alarm
AL16
Pressure upper limit alarm
AL17
Flowrate upper limit alarm+Pressure upper limit alarm
AL18
Temperature lower limit alarm+Pressure upper limit alarm
AL19
Flowrate upper limit alarm+Temperature lower limit alarm+Pressure
upper limit alarm
AL20
Temperature upper limit alarm+Pressure upper limit alarm
AL21
Flowrate upper limit alarm+Temperature upper limit alarm+Pressure
upper limit alarm