7
• Provide a straight pipe section in upstream side and downstream side of the
installation location.
Refer to the drawings below for the length of upstream pipe section. D indicates
the connecting port size. Secure the length of more than 5D for the downstream
pipe section.
• If the oil, water or dust is contained in a fluid, install a device to remove them.
If the oil, water or dust is contained in a fluid, they might cause measurement
error or faulty operation.
Note
• Remove the water using a dryer so that it does not cause dew condensation in
the pipe.
• Use a dust-eliminating filter of less than 1µm mesh.
• Use an oil-eliminating mist separator with the eliminating capability of resid-
ual oil density less than 0.01mg/m
3
.
Pipe with three-
dimensional double
90
°
bend
Pipe with single-plane
double 90
°
bend
Pipe with 90
°
bend
Enlarging pipe
Reducing pipe
Type of Installation
Flow direction
10D min.
5D min.
10D min.
5D min.
10D min.
5D min.
10D min.
20D min.
5D min.
5D min.
Flow direction
Flow direction
Flow direction
Flow direction
Chapter 3. INSTALLATION, MOUNTING, WIRING