3-5 : Master/slave configuration
This function is used to minimize magnetic interference by detectors installed closely
each other in the multiple head filling machine applications. A master converter sends
synchronized signal for excitation to slave converters, thus avoiding output error due
to magnetic interference.
According to the model number selected, the configuration for a master or slave is
done by the factory.
Master converter: MGR13C-**M
Slave converter: MGR13C-**S
In case of configuring master/slave function, follow below procedure.
(1) Turn OFF the power.
(2) Loosen screws of the main unit fixed in slot 1 and remove the main unit.
(3) Set the DIP switch as shown in the Figure 6.
Figure 6
M
S
1 2 3 4
1 2 3 4
Master converter Slave converter