![Azbil MagneW 3000 User Manual Download Page 10](http://html1.mh-extra.com/html/azbil/magnew-3000/magnew-3000_user-manual_3042663010.webp)
Overview
Azbil Corporation
6
Model MGR13C/MGR11U - MagneW3000 Electromagnetic FLowmeter Hyper-Fill
2-3-2 : Pulse output wiring
The pulse output is an open collector output. Pay attention to voltage and polarity
when wiring.
External power supply voltage
12 to 24V DC (30V max.)
Output current
100 mA max.
Transient response
5
μ
S typ.
Power supply
voltage
Voltage drop (closed
circuit) (HIGH voltage)
Voltage drop (Open
circuit) (LOW voltage)
24V DC
19V min.
2.5V max.
12V DC
7V min.
2.5V max.
Figure 3 Wiring diagram for pulse output
This is impossible.
External power supply
12 to 24V DC (30V DC max.)
100mA max.
P
P
Protective diode
Load