Model MGR13C/MGR11U - MagneW3000 Electromagnetic FLowmeter Hyper-Fill 

3 :  Configuration of the converter

Refer to the following configuration table printed to the main unit for the converter 
configuration.

3-1 : Range

Select an appropriate range. It is recommended to set a range so that the flow rate is 
approximately 70%. Do not set a range of which the flow rate is less than 25%. 

Select the range by receptacles in S2 shown in Figure 5.

3-2 : Pulse scale

0.1 mL/P or 0.05 mL/P is selectable as a pulse scale.

Pulse scale of 0.05 mL/P is not applicable in case of range of 800 mL/s. 

~Note

*  Pulse width of 200 

μ

S is not applicable in case that pulse span fre-

quency fs is 8000 Hz.

Figure 5  

Range

100 mL/s

200 mL/s

400 mL/s

800 mL/s

Range

100 mL/s

200 mL/s

400 mL/s

800 mL/s

Pulse span 
frequency fs

0.05 mL/P

2000 Hz

4000 Hz

8000 Hz *

   N/A

 0.1 mL/P

1000 Hz

2000 Hz

4000 Hz

8000 Hz *

S2

S3

S4

100mL/s

100mL/s

200mL/s

200mL/s

400mL/s

400mL/s

800mL/s

800mL/s

RANGE

PULSE WEIGHT

RANGE

PULSE WIDTH

0.1mL/P

0.05mL/P

0.05mL/P

0.05mL/P

0.1mL/P

0.1mL/P

0.1mL/P

30

μ

s

200

μ

s

Summary of Contents for MagneW 3000

Page 1: ...MagneW 3000 Electromagnetic Flowmeter Hyper Fill Model MGR13C Converter MGR11U Detector User s Manual CM2 MGR100 2001 2nd edition...

Page 2: ...s the implied warranties of mer chantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer In no event...

Page 3: ...tion 3 2 3 Wiring 4 2 3 1 Converter wiring 4 2 3 2 Pulse output wiring 6 2 3 3 Master slave wiring 7 3 Configuration of the converter 8 3 1 Range 8 3 2 Pulse scale 8 3 3 Pulse width 9 3 4 Drop out 9 3...

Page 4: ......

Page 5: ...c FLowmeter Hyper Fill 1 1 Overview MagneW 3000 Hyper Fill is developed for high speed batching and filling machine applications Hyper Fill is a magnetic flowmeter optimized for the sophisticated meas...

Page 6: ...ugh the rubber bush and mount the converter Handle the rubber bush with care because the rubber bush isolates the converter housing from the mounting wall 3 Locate the converter so that switches and t...

Page 7: ...sh water before connecting the model MGA23W cable 5 After connecting the model MGA23W cable tighten the screw of the water proof connector and tighten the belt of the water proof cover to keep water a...

Page 8: ...first After connecting wires to the terminals of A1 to A4 B1 to B4 and C1 to C4 install the shield plate as shown in the Figure 1 The shield plate is fixed by two screws Refer to the following table...

Page 9: ...to the special cable model MGA23W for main unit 3 Flow rate signal Excitation A4 B4 C4 X4 Y4 Connect to the special cable model MGA23W for main unit 4 Flow rate signal Excitation P1 P1 Connect to puls...

Page 10: ...when wiring External power supply voltage 12 to 24V DC 30V max Output current 100 mA max Transient response 5 S typ Power supply voltage Voltage drop closed circuit HIGH voltage Voltage drop Open cir...

Page 11: ...should be negligible in the multiple head filling machine applications Master slave cable carries synchronized signal for excitation so as to minimize magnetic interference Each converter should be co...

Page 12: ...in S2 shown in Figure 5 3 2 Pulse scale 0 1 mL P or 0 05 mL P is selectable as a pulse scale Pulse scale of 0 05 mL P is not applicable in case of range of 800 mL s Note Pulse width of 200 S is not ap...

Page 13: ...s used to set the dropout value for the pulse output The pulse output will be cut off below the setting value to avoid flow pulsation in range value close to zero thus preventing incorrect totalizatio...

Page 14: ...nal for excitation to slave converters thus avoiding output error due to magnetic interference According to the model number selected the configuration for a master or slave is done by the factory Mas...

Page 15: ...remain inside of the flowtube Bubbles will prevent accurate measurement 4 2 Zero adjustment A zero adjustment is very important for accurate flow rate measurement Follow the procedures according to t...

Page 16: ...ive seconds then light on If failed LED blinked for 20 seconds Check if wiring is correct and no bubble remains in the flowtube and try zero adjustment again Version 2 is compatible with Version 1 Ver...

Page 17: ...Note...

Page 18: ......

Page 19: ...ent Number CM2 MGR100 2001 Document Name MagneW 3000 Electromagnetic Flowmeter Hyper Fill Model MGR13C MGR11U User s Manual Date 1st edition Mar 2005 2nd edition Aug 2012 Issued Edited by Azbil Corpor...

Page 20: ......

Reviews: