AB-6584
7
Input/Output Terminal Arrangement
Figure 3. Example of input/output terminal arrangement
Note:
Fig. 3 shows an application example. Other applications that satisfy input/output specifications are applicable as well. For applicable inputs
and outputs of each Infilex AC model, refer to Table 1.
Table 1. Applicable inputs/outputs for each model number
Model number
AI1 to
AI4
AO1,
AO2
AO3 AO4 AO5
AO6
DI1 to
DI4
DI5,
DI6
DI7,
DI8
DO1,
DO2
DO3 DO4 DO5
DO6
WY5317C0100
9
9
9
9
9
WY5317C0200
9
9
9
9
9
9
9
WY5317C0300
9
9
9
9
9
9
9
9
9
9
9
WY5317C0400*
9
9
9
9
9
9
9
9
9
9
9
9
9
9
∗
Note:
An I/O module can be added to Model WY5317C0400. For the applicable I/O module, refer to AB-6527 Specifications/Instructions of Model
RY50XX.
LC-bus
24 V AC
Voltage output
(2 to 10 V /
0 to 10 V)
Temperature
input
(-20 to 80
°
C)
Relay output
(for momentary only)
(24 V AC/DC)
1
2
3
4
5
6
7
8
9
10
11
12
DO1
DO2
DO3
DO4
DO5
DO6
13
14
15
16
17
18
19
20
21
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
IN
OUT
CONF
(COM)
AI1
AI2
AI3
AI4
AO1
AO2
AO3
AO4
AO5
AO6
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
(COM)
(+)
(COM)
(+)
(+)
(COM)
(+)
(+)
(COM)
(+)
Relay output
(for momentary
/maintained)
(24 V AC/DC)
Voltage input
(1 to 5 V)
Digital input
(current: 5mA
voltage: 24 V DC)
Applied from
Infilex AC
Fan ON/OFF
Fan ON/OFF
Humidifier
Outdoor air damper
Return air temperature
Supply air temperature
Return air humidity
Multi-purpose voltage input
Supply air fan status
Supply air fan alarm
Return air fan status
Return air fan alarm
Filter alarm
Water-leakage alarm
Multi-purpose input
Multi-purpose input
Hot water valve, chilled/hot
water valve
Chilled/hot water valve
Outdoor/exhaust air
damper, return air damper
Supply air temperature
Return air humidity
Example of
Terminal arrangement
Example of
Terminal arrangement