Azbil Infilex WY5317C Specifications & Instructions Download Page 2

AB-6584 

Safety Instructions 

Please read instructions carefully and use the product as specified in this manual.  Be sure to keep this manual near by for ready 
reference.  

Usage Restrictions 

This product is targeted for general air conditioning.  Do not use this product in a situation where human life may be affected.  If 
this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil 
Corporation’s sales representative.  Azbil Corporation will not bear any responsibility for the results produced by the operators.

 

 WARNING  

 

  DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product 

power supply before performing any wiring. 

 

  Be sure to ground with 100 

Ω

 or lower ground resistance.  Improper grounding may cause electrical shock or

equipment damages. 

 

  Do not detach the terminal cover at any time except when wiring.  After wiring, be sure to attach the terminal cover. 

Before attaching/detaching the terminal cover, make sure that the wires are not current-carrying to prevent 
electrical shock. 

 

  Disconnect power before the product replacement to prevent electrical shock. 

 

  Wire strip length to be connected to the quick-fit screwless terminal block must be 8 mm.  If the strip length is longer 

than 8 mm, the conductor will be exposed, causing electrical shock or short circuit between adjacent terminals.  If 
it is shorter, the conductor will not contact the connector. 

 

  Do not disassemble the product.  Disassembly may result in electrical shock or equipment damage. 

 

  

CAUTION 

 

  Installation and wiring must be performed by qualified personnel in accordance with all applicable safety 

standards. 

 

  Installation must be carried out according to the operating conditions (power, temperature, humidity, vibration, 

shock, installation position, atmospheric condition, etc) specified in this manual to prevent equipment damages.

 

  All wiring must comply with local codes of indoor wiring and electric installation rules. 

 

  Install a circuit breaker or circuit protector in the power supply circuit that supplies the power to the product. 

 

  Use crimp terminal lugs with insulation for electric wires connected to the screw terminals. 

 

  Connect cables to the power source with terminals or the like for permanent connection. 

 

  Make sure all the wires are tightly connected to prevent heat generation or equipment damages. 

 

  If more than the rated power supply voltage is applied, product replacement is required for safety. 

 

  Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel cabinet) 

 

  Lightening protection based on the regional characteristics and the building structure is needed to minimize 

equipment damages.

 

 

  Noise protection is necessary when the product is installed in a location close to many noise sources. 

 

  Do not block the vent holes of the product to prevent equipment damages.  Remove protective sheet after 

installation and wiring. 

 

  After mounting the product on DIN rail, make sure that the holding parts of all the modules are properly fixed with 

their whole parts lifted.  The product may drop from the DIN rail and be damaged due to improper mounting. 

 

  Dispose of the lithium battery in accordance with your local regulations.

 

 

  Dispose of this product in accordance with your local regulations.  Do not reuse all or a part of this product.

 

Trademark information: 
Infilex, Neopanel, PARAMATRIX and savic-net are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries. 
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). 
CompactFlash is a U.S. registered trademark of SanDisk Corporation. 
KPEV is a registered trademark of Furukawa Electric Co., Ltd. 
LonTalk is a trademark of Echelon Corporation registered in the United States and other countries. 

Summary of Contents for Infilex WY5317C

Page 1: ...number of its I O points which allows external cooling control humidification and other AHU controls User interface module Operator Panel Operator Panel panel mount type integral type connected to Infilex AC allows you without changing the settings from the BMS center unit to change the Infilex AC settings Remote control with a user terminal Neopanel or Neoplate is connectable so that a user at a ...

Page 2: ...atmospheric condition etc specified in this manual to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Install a circuit breaker or circuit protector in the power supply circuit that supplies the power to the product Use crimp terminal lugs with insulation for electric wires connected to the screw terminals Connect cables to the pow...

Page 3: ...ote units sub controllers can be connected Max wiring length of LS bus is 900 m Infilex GC Model WY5311 Infilex AC Model WY5317C Infilex ZM Model WY5322 Infilex VC Model WY5306 Infilex FC Model WY5305 Infilex VC Model WY5306 LS bus LonTalk protocol Neoplate Analog user terminal Neopanel Digital user terminal SMS Client PC Infilex AC Model WY5317C Infilex GC Model WY5311 Infilex GD Model WY5310 PMX...

Page 4: ...4 Temperature input 2 pts voltage input 2 pts digital input 8 pts voltage output 6 pts relay output 6 pts 1 user interface module and or 1 I O module can be combined e g for proportional humidifying control outdoor air cooling control the same as Model WY 5317C03 outdoor air cooling control 00 Fixed Notes For I O modules and user interface modules UT module and Operator Panel to be combined with I...

Page 5: ...ee contact Input signal RTD Pt 100 Ω 0 C Temperature input Measuring range 20 C to 80 C Input voltage range 1 V to 5 V Input Voltage input Input impedance 500 kΩ Output method Relay output N O contact N O contacts share the same common line Max 24 V AC 0 5 A inductive load cos φ 0 4 or more Contact rating Max 24 V DC 0 5 A Relay output normally open N O contact Min applicable load 5 V 10 mA Output...

Page 6: ... stripped length 8 mm pin terminal cannot be used Organize the cables with cable binding bands so as not to hide LED battery holder or tag JIS Japanese Industrial Standards KPEV is a wiring standard provided by Furukawa Electric Co Ltd JCS Japanese Electric Wire and Cable Makers Association System common Ground line is used as a common line for signal transmission Actuator damper thus has to have ...

Page 7: ...V Temperature input 20 to 80 C Relay output for momentary only 24 V AC DC 1 2 3 4 5 6 7 8 9 10 11 12 DO1 DO2 DO3 DO4 DO5 DO6 13 14 15 16 17 18 19 20 21 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 IN OUT CONF COM AI1 AI2 AI3 AI4 AO1 AO2 AO3 AO4 AO5 AO6 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 COM COM COM COM Relay output for momentary maintained 24 V AC DC Voltage input 1 to 5 V Digital input curr...

Page 8: ...AB 6584 8 Dimensions Figure 4 Dimensions mm 60 140 90 ...

Page 9: ...Data Setter adaptor Part No DY5301S0000 For details of Data Setter adaptor Part No DY5301S0000 refer to its Specifications manual see Note Figure 6 Connection example of Data Setter with Data setter adaptor to LC bus port CONF port of Infilex AC LED for operating status S1 switch Do not press S1 switch Battery holder Indication tag DIN rail mounting hook Infilex AC Model WY5317 Infilex GC Model WY...

Page 10: ...ithium battery with the power ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Figure 7 Battery replacement 1 Pull out the battery holder using a slotted screwdriver 2 Disconnect the battery connector and detach the lithium battery from the battery holder 3 Place a new lithium battery in the bat...

Page 11: ...after the power is turned on During this time the LED on the front lights up temporarily but this does not indicate an error Be sure to use a small power circuit to turn on off the fan Be sure to use a shielded wire for the signals output to the inverter Leave at least 35 mm clearance between the top bottom surfaces of the product and other devices Peel off the protective sheet on the top surface ...

Page 12: ...AB 6584 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 3 0 Sep 2015 AB 6584 H W03 J AI 6584 Rev 3 1 Printed in Japan 12 ...