NOTE:
Leaked sulfuric acid leak is dangerous. If
contacts skin, rinse with water affected parts
immediately for at least 15 minutes.
Fig.8 Mounting Dust Filter
Action Confirmation
After installation wait 10 minutes for the sensor to
stabilize. Then, check its output value against the
appropriate expected range.
Table 2
Place Range
Outdoor
0 to 3 ppm
Outdoor (near traffic)
5 to 10 ppm
Clean air office
0 to 5 ppm
Office
5 to 10 ppm
Clean air parking lot
3 to 15 ppm
Parking lot
15 to 30 ppm
Next, light a cigarette and blow the smoke over sensor.
Check that the CO concentration increases sharply
within one minute.
CAUTION
●
Do not install in locations where flammable
gas may be present.
Sensor Cover
Fixing Screws
CO Gas Sensor
Fixing Screws
Filter Cover
Dust Filter