background image

 

Specifications are subject to change without notice.

 

 

Building Systems Company 

 

 

 

http://www.azbil.com/  

 

 

Rev.1.2  Jun. 2014 

AB-5782 

 

 

NOTE: 

Leaked sulfuric acid leak is dangerous.    If 
contacts skin, rinse with water affected parts 
immediately for at least 15 minutes. 

 

Fig.8  Mounting Dust Filter 

 

Action Confirmation 

 

After installation wait 10 minutes for the sensor to 
stabilize.    Then, check its output value against the 
appropriate expected range. 

 

Table 2 

Place Range 

Outdoor 

0 to 3 ppm 

Outdoor (near traffic) 

5 to 10 ppm 

Clean air office 

0 to 5 ppm 

Office 

5 to 10 ppm 

Clean air parking lot 

3 to 15 ppm 

Parking lot   

15 to 30 ppm 

 

 

Next, light a cigarette and blow the smoke over sensor.   
Check that the CO concentration increases sharply 
within one minute. 

 

 CAUTION 

 

  Do not install in locations where flammable 

gas may be present. 

 

 
 
 
 

 

 

Sensor Cover 

Fixing Screws 

CO Gas Sensor

Fixing Screws 

Filter Cover 

Dust Filter

Reviews: