AB-5782 

Installation Site 

When installing in indoor parking lots, ensure the follow-
ing requirements are satisfied: 

1) Air flow from the fan must reach the CY7200A. 
2) Install 2 to 2.5 m above floor level. 
3) Install in a position where the CY7200A does not come 

into direct contact with exhaust fumes. 

4) Do not install near fan. 
5) Install at least one CY7200A sensor on each floor of a 

multi-story indoor garage.    Install at least one sensor 
in each area, if partitions segregate a floor into 
multiple spaces. 

 

System Configuration (ventilation fan control for 
indoor parking lots) 

Fig.4  System configuration 

 

Installation (main unit) 

1) Fasten the painting clearance cover with 66.7 mm 

pitch (box cover, JIS C8336) on a standard outlet box. 

2) Fasten the mounting plate on the painting clearance 

cover. 

3) Fasten the base plate on the mounting plate. 
4) Connect the wires. 
5) Remove the cover from the sensor/transmitter and 

fasten the sensor/ transimitter on the base plate. 

6) Fit the cover to the sensor/ transmitter.     

Note:    Order the base plate separately 

 

Fig.5  Installation (main unit) 

 

Fig.6    Cover with painting clearance complying with JIS 

(for medium-sized square box, puchase locally) 

 

Table 1 

Lead wire color 

Signal 

Red 

4 to 20mA DC (+) 

Blue 

4 to 20mA DC (–) 

 

Fig.7  Wiring 

 

 

Install dust filter 

Always install a dust filter when the sensor is to be in-
stalled in locations, such as bus terminals, where dust 
and other contaminants are present. 

Generally there is no need to install at dust filters on 
sensors installed in underground parking lots. 

 

NOTE: 

Follow the instructions when wiring. 

 

Do not break or short wiring.    Faulty wiring may 

cause damage to the sensor. 

 

Do not incorrectly wire 24V DC and 100/ 200V 

AC. 

 

Put the controller electric input between the 

sensor side (blue) and electric side. 

 

Set the Co sensor element ion circuit. 

 

1) Turn the power OFF and stop power supply.   
2) Remove sensor cover. 
3) Put filter cover inside filter.    Make net face toward the 

element. 

4) Cover sensor.    Insert screws vertically. 
5) Tighten both screws evenly and in turn. 
6) Check filter cover is correctly installed on element 

before attaching to cover. 

 

NOTE: 

Always dispose of the sensor in an appropriate 
manners.    The CY7200A should be treated as 
industrial waste, sensor contains sulfuric acid. 

 

 

 

 

 

Communication with central 
control system 

CO concentration 

 transmitter CY7200A 

Azbil Corporation 

controllers WY7211 

and WY7217 

Ventilation fan

 ON-OFF 

 Multi-stage 

 Inverter 

Red (+)

Blue (–)

DC24V 
(+)

DC24V 
( )

AC power source
(100/ 200 A) 

To electric input of controller 

 (+)

 (–)

CY7200A

RY7910D 

Max

1.5

89

106

60 106 

13

66 ± 0.4 

Base plate (order separately) 
83152965-001 

Base 

Lead wire 

Base plate mounting screw 
(M3-5 mm x 2) 

Mounting plate 

Painting clearance cover

Base plate 

Mounting plate mounting 
screw M4-8 mm × 2 

Cover 