background image

AB-7350-U 

© 2015–2016 Azbil Corporation All Rights Reserved. 

Specifications/Instructions

ACTIVAL

 Flow Measurement and Control Valve 

Standalone Model 

Motorized Two-Way Valve with Flanged-End Connection  

(145 psig / Gray cast iron)* 

 

 

 General 

ACTIVAL

 Flow Measurement and Control Valve Model 

FVY5137J is a series of motorized two-way valves with 
flanged-end connection. 1

1

/

2

” to 3" rotary valve and actuator are 

integrated in a single unit. 

In combination with the functions of a control valve, Model 
FVY5137J measures and controls flow. Model FVY5137J thus 
enables to control temperature for air conditioning by controlling 
chilled/hot water volume and to measure chilled/hot water flow. 

For such a high functionality, compact size and simple 
installation of Model FVY5137J are incomparable. 

Model FVY5137J is operated by the following control signal. 

  -  4 to 20 mA DC input: 

Provides proportional control in combination with a single 
loop controller. (e.g., Model SDC35/SDC36) 

Flow data stored in Model FVY5137J is retrieved via RS-485 
communication (Modbus protocol). The retrieved flow data is 
effective for energy-saving facility operation. 

 

 

 Features 

 

Compact and lightweight: 
Rotary valve actualizes small body and light weight. 

 

Valve and actuator integrated in a single unit. 

  Model FVY5137J holds flow data effective for 

maintenance and energy-saving facility operation. The 
data is retrieved via RS-485 communication (Modbus 
protocol). 

 

Valve for chilled/hot water control applicable to large Cv 
value, high rangeability, and low leakage. 

 

Durable actuator with low power consumption. 

 

 

Flow control/position control operation selectable: 
For flow control, flow characteristic is selectable (equal 
percentage or linear). For position control, flow 
characteristic is equal percentage. 

 In combination with Display Panel (Model 

QY5010S1000) and the insertion-type pipe temperature 
sensor (Model TY7830) or the temperature sensor for 
pipe surface (Model TY7820), pressure, temperature, 
and flow can be displayed on the Display Panel. 

 

CE Marking certified product: 
Models FVY5137J conforms to all the applicable 
standards of CE Marking. 

 

IMPORTANT: 
 

Do not use the data measured by Model FVY5137J for charging or dealing purposes. 

 
 
 
 
 
 
 
 
*  This product was designed and manufactured conforming to the ISO (International Organization for Standardization, PN10/GG-20). 

Summary of Contents for ACTIVAL FVY5137J

Page 1: ...retrieved flow data is effective for energy saving facility operation Features Compact and lightweight Rotary valve actualizes small body and light weight Valve and actuator integrated in a single un...

Page 2: ...ls weigh more than 40 lb 18 1 kg Carefully move the product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product dam...

Page 3: ...ouch the moving parts of the product Doing so might cause injury Do not carelessly touch this product when being used to control hot water The product temperature is hot and you might get burned Do no...

Page 4: ...to 17 C and 113 to 149 F 45 to 65 C ranges 29 to 261 psig pipe pressure and 4 35 to 43 5 psig differential pressure Without these ranges the flow rate measuring accuracy might decrease To keep flow me...

Page 5: ...resistance Between the case and terminal Min 5 M 50 V DC Dielectric strength Between the case and terminal 250 V AC for 1 min leakage current 5 mA or less Position for shipment 100 fully open preset...

Page 6: ...4 pin connector Operation status indicator LED 1 red LED Status LED indication Normal Repetition of 1 second ON 1 second OFF Major alarm Continuous ON Minor alarm Repetition of 1 second ON 0 25 second...

Page 7: ...4 C at 0 to 80 C ambient temperature 1 08 F at 4 to 32 F 0 6 C at 20 to 0 C ambient temperature Error due to wiring length 0 27 F at 49 2 49 2 ft 0 15 C at 15 15 m in the 32 to 176 F 0 to 80 C measur...

Page 8: ...with the sensor 98 ft 30m 6 pin 3 pin 2 connector Insertion type pipe temperature sensor AWG 22 x 3 core 0 3 mm 2 98 ft 30m RS 485 communication AWG 16 24 x 2 pairs of shielded twist pair cable 1 pair...

Page 9: ...24 190 90 20 140 180 19 16 kg FVY5137J0081 S03 3 in 10 35 4 92 7 99 3 94 0 87 6 00 7 48 0 75 4 45 0 lb DN80 mm 263 125 203 100 22 152 4 190 19 20 4 kg Figure 1 Dimensions Parts Identification 1 to 3 v...

Page 10: ...rature Row T2 Return water temperature Reset switch Connector for Display Panel 24 V AC Power Port for Display Panel cable Port for temperature sensor Pt100 input cable Port for valve sensor cable Por...

Page 11: ...the inflow side of the piping Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product After installation make sure no fluid leaks f...

Page 12: ...tor in water Although the product can be used outdoors be sure not to expose the product to direct sunlight Provide the outdoor cover optional to install outdoors Install the product in a position all...

Page 13: ...alve The valve cannot fully close or the valve seat may get damaged causing fluid leakage due to an object jammed inside the valve When piping do not apply too much sealing material such as solidifyin...

Page 14: ...lly open close the product do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the product slowly turn the joint If shock is sent to the actuator the actuator might ge...

Page 15: ...connector Use crimp terminals with insulation for connections to the product terminals Failure to do so might cause short circuit leading to fire or device failure Firmly tighten the terminal screws...

Page 16: ...sensor Pt100 input Figure 13 6 pin connector for temperature sensor Pt100 input Terminal Wire color Description Temperature sensor for pipe surface Insertion type pipe temperature sensor T1A Red Red P...

Page 17: ...of the recommended cable 1 Pass the 4 core cable of Display Panel through the actuator port for Display Panel See Fig 3 for the location of the port 2 Strip the wire sheath Strip length is 0 31 8 mm...

Page 18: ...es of RS 485 communication cable to the connector unplugged from the actuator socket After connecting the wires to the connector plug the connector into the socket Do not use terminators Do not connec...

Page 19: ...er with multiple 4 to 20 mA input type products See Figs 22 and 23 4 to 20 mA control signal input is not isolated from the power and the 4 to 20 mA input impedance is 250 For connecting a controller...

Page 20: ...Refer to 6 Single transformer with two products in the Precautions for connection section Figure 23 Connection example Two Model FVY5137 with a single controller and a single transformer Notes 1 Prov...

Page 21: ...lizing pulse output open collector output Model FVY5137J This product 3 4 V Protection diode Magnetic counter 0 V Figure 28 Connection example Magnetic counter with relay coil Figure 26 Connection exa...

Page 22: ...ed by cable glands use waterproof plica tubes etc Item Model number Applicable cables Three port unit is used 83104346 012 0 24 Dia to 0 31 Dia 6 mm Dia to 8 mm Dia 83104346 013 0 28 Dia to 0 35 Dia 7...

Page 23: ...the cable gland with three ports Refer to the below table and tighten each part of the cable gland to connect it onto a wiring port knockout of this product Part of cable gland with three ports Fasten...

Page 24: ...erminal connector to facilitate connecting wires 5 Loosen the cap of a seal connector Let the wires through the seal connector so that the end of the sheath comes to inner side of the cover Then tight...

Page 25: ...be re crimped on the wire ends Keep the margins therefore to arrange the cables IMPORTANT Do not put heavy load on the joint of the cable gland with the product Detaching the cable gland with three p...

Page 26: ...If your problem is not solved by the corresponding action please contact our salesperson serviceperson Table 1 Inspection items and details Inspection item Inspection interval Inspection detail Visua...

Page 27: ...AB 7350 U 27 Figure 34 Check of the valve position detecting accuracy Pointer 0 39 1 cm Lower setscrew of the terminal cover 0 39 1 cm...

Page 28: ...AB 7350 U Rev 4 0 Jun 2016 AB 7350 U 28 ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries...