8.3
Setting the system voltage with SMA SB Storage
To add Energypacks, the system voltage must be adjusted to the module voltage. For this purpose, set
the Sunny Boy Storage to a specific SOC:
1.
Open the user interface of the Sunny Boy Storage.
2.
Register as installer.
3.
Select device parameter and click on
Edit Parameter
.
4.
enter the desired SOC under
Battery - External Default
and confirm in the Web UI above
with
Save All
.
Example:
new Energypack with 50.1 V
–
corresponds to approx. 35 % SOC
AXIstorage is at 60 % SOC
–
so set the
Lower battery discharge limit
to 35 % and
confirm with
Save All
.
5.
battery system goes automatically to parameterized SOC and stops with this state of
charge.
6.
install a new battery module. See chapter 3.3.4 from point 3.
NOTE: All voltage specifications refer to the open circuit voltage (OCV).
Voltage
System voltage with number of serial battery modules
Energypack
SOC
3
4
5
6
46.3 V
0%
138.9 V
185.2 V
231.5 V
277.8 V
47.8 V
10%
143.5 V
191.3 V
239.1 V
287.0 V
48.8 V
20%
146.4 V
195.2 V
244.1 V
292.9 V
49.7 V
30%
149.1 V
198.8 V
248.5 V
298.2 V
50.5 V
40%
151.5 V
202.0 V
252.5 V
302.9 V
51.5 V
50%
154.4 V
205.9 V
257.4 V
308.9 V
52.7 V
60%
158.0 V
210.6 V
263.3 V
315.9 V
53.6 V
70%
160.9 V
214.6 V
268.2 V
321.9 V
54.8 V
80%
164.5 V
219.3 V
274.1 V
329.0 V
55.9 V
90%
167.7 V
223.6 V
279.6 V
335.5 V
56.7 V
100%
170.1 V
226.8 V
283.5 V
340.2 V
8.4
Glossary
Term
Definition
User
Individual who uses the product
Specialist
An individual who, based on his or her relevant professional education, training and/or
experience, is capable of identifying risks and preventing hazards arising from the use of the
product.
Hazard
Potential source of damage
Damage
Physical injury or damage to the health of persons, or damage to property or the environment
Thermal runaway
Chemical process that is triggered by heat and generates additional heat.
Table 6:
OCV and SOC of the Energypack and the AXIstorage