UMAX090600 Version 1
Preliminary Documentation – May be Subject to Change
28-48
3.2.
Name, Address and Software ID
3.2.1.
J1939 Name
The CAN-BC-LED Controller ECU has the following defaults for the J1939 NAME. The user should refer to
the SAE J1939/81 standard for more information on these parameters and their ranges.
Arbitrary Address Capable Yes
Industry Group
0, Global
Vehicle System Instance
0
Vehicle System
0, Non-specific system
Function
141, Battery Charger
Function Instance
3, AX090600, 24VDC to 14VDC 2A Battery Charger
ECU Instance
0, First Instance
Manufacture Code
162, Axiomatic Technologies Corporation
Identity Number
Variable, uniquely assigned during factory programming for each ECU
The ECU Instance is a configurable setpoint associated with the NAME. Changing this value will allow multiple
ECUs of this type to be distinguishable by other ECUs (including the Electronic Assistant
) when they are
all connected on the same network.
3.2.2.
ECU Address
The default value of this setpoint is 26 (0x1A), which is the address representing an
Alternator/Electrical
Charging System
by SAE in J1939 tables B3 to B7. Electronic Assistant will allow the selection of any address
between 0 to 253, and
it is the user's responsibility to select an address that complies with the
standard
. The user must also be aware that since the unit is arbitrary address capable, if another ECU with
a higher priority NAME contends for the selected address, the CAN-BC-LED will continue select the next
highest address until it find one that it can claim. See J1939/81 for more details about address claiming.