PEE1V03
20-11- 2017
6
Type of pulses
IB by LST EN1434-2
Maximum permissible frequency of input pulses
3 Hz
Maximum permissible voltage of input pulses
3,6 V
Condition of maintenance of high level
3,6V via 3,3M
resistor
Temperature measurement
Temperature measuring ranges (for calculator)
0
o
C....180
o
C.
Temperature difference measuring range
3K......150
K* or 2 K
…150 K*
Temperature sensor :
-
Platinum resistance temperature sensors
Pt500
(corresponding EN60751 and are selected
(or Pt1000
–according to the special order)
as matched pairs under requirements EN1434
and MI004 of Directive 2014/32/EU)
-
For meters with threaded
Direct mounted short probes type DS
connection G
3
/
4
, G1 or G1 ¼
in accordance with LST EN1434-2
-
For other types of connection
Pocket mounted long probes type PL
in accordance with LST EN1434-2
2-wire connection method, cable length:
up to 5 m
Note: * -
depending on the lower limit of the temperature difference of the connected pair of temperature
sensors.
Display (LCD)
The device is equipped with 8-digits LCD (Liquid Crystal Display) with special symbols to display
parameters, measurement units and operation modes
The following information can be displayed: integral and instantaneous measured parameters, and archive
data, and device configuration information listed in p.6.3.
Display resolution of energy:
00000001 kWh, 00000,001 MWh (Gcal or GJ)
Display resolution of volume:
00000,001 m
3
Data registration and storage
Every hour, day and month values of the measured parameters are stored in memory of the meter
All data from archive can be read only by means of the remote reading (see p.6.5)
In addition data logger records of monthly parameters can be seen on the display (see p. 6.3.1)
Following hourly, daily and monthly parameter values are recorded in heat meter memory:
1
Integrated energy
2
Integrated cooling energy
3
Integrated energy of tariff 1
4
Integrated energy of tariff 2
5
Integrated volume of liquid
6
Integrated pulse value in pulse input 1
7
Integrated pulse value in pulse input 2
8
Maximum thermal power value for heating and date
9
Maximum thermal power value for cooling and date
10
Maximum flow rate value and date
11
Maximum value of flow temperature of heat conveying liquid and date
12
Maximum value of return temperature of heat conveying liquid and date
13
Minimum value of flow temperature of heat conveying liquid and date
14
Minimum value of return temperature of heat conveying liquid and date
15
Minimum value of temperature difference and date
16
Average value of flow temperature of heat conveying liquid
17
Average value of return temperature of heat conveying liquid
18
Operating time without an error of thermal energy calculation
19
Total error code
20
Time when the flow rate exceeded 1.2 qs
21
Time when the flow rate was less than qi
Data logger
capacity:
up to 1480 h
– for hourly records.
up to 1130 days -. for daily records,
up to 36 last months -. for monthly records,
Archive data storage time not less than 36 months
Storage time of measured integrated parameters
even if device is disconnected from power supply:
not less than 15 years