Axi FPS Compact Series Instruction, Operating, & Maintenance Manual Download Page 9

 

REV0302COM010120 

if the inlet port of the system is located above the lowest possible level of fuel in the tank. Additionally, a priming tee 
should be installed at the highest point of the suction line to enable priming of the pipelines and system.  
 
The return line(s) should be plumbed to the system’s outlet port (located on the right-hand side of the system) and enter 
the tank as far as possible away from the pick-up tube, close to the tank bottom. 
 
Multiple suction and/or return lines may be connected to a manifold outside the system. 
 

Note: Anti-Siphon or other external plumbing devices may be required by state and/or local regulations & code.  

 
Cumulatively, the system capabilities are 10 FT. (3.05 m) suction (vertical lift), when connected to the minimum 
recommended piping size (Ref.: Page 4 – Inlet/Outlet Port), or more, with no additional flow restrictions. That includes 
valves, 90-degree connectors, or other plumbing accessories. For continuous optimal performance, make sure suction 
and discharge lines are free of contamination, nothing is blocking the flow of fuel, and the suction line always stays 
primed.  
 

Note: Plumbing installation must be in accordance with all applicable federal, state, and local rules, laws, standards, and 
regulations. 

Typical Plumbing Installation (Schematically) 

See provided P&ID drawing(s). 

Important Installation Precautions 

The suction line of the system should be independent and separate from the suction line of the engine. If that is not 
possible, appropriate valves must be installed separate to the system from the engine fuel system to prevent any possible 
interference with safe engine operation.  
 
It is highly recommended to plumb the discharge line independent and separate of the engine’s fuel return line back to the  
tank. If the return line from the engine and the discharge of the system must be combined in any way, adequate valves 
should be installed to prevent any possible interference with safe engine operation. 
 

 

Summary of Contents for FPS Compact Series

Page 1: ...on Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com FPS FPS Compact Instruction Operating Maintenance Manual COMPACT FUEL MAINTENANCE SYSTEM REV030...

Page 2: ...REV0302COM010120 1...

Page 3: ...ly 8 Important Installation Precautions 8 Controller 9 Setting the Current Date and Time 9 Programming the Timer 9 Priming the System 10 Priming Procedure 10 Commissioning Initial Start Up 11 Gauge Ve...

Page 4: ...ose Barb System Back Plate Powder Coated Aluminum Operating Temperature 41 104 F 5 40 C Electrical 12VDC 10A or 24VDC 5A Pump DC Gear Pump Suction Capability Primed 10 ft 304 8 cm Total Dynamic Head T...

Page 5: ...tch Water Detection Alarm Module Vacuum Switch Leak Detection Float Switch Pump Motor DC Gear Pump Primary Filter Water Separator Fuel Filter o Standard issue back flushable 30 micron hydrophobic filt...

Page 6: ...tion o Activated when the Float Switch in the system s drip tray detects a raised liquid level The system will go into an alarm state and the pump will not be allowed to be run until the alarm is addr...

Page 7: ...ectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that could...

Page 8: ...r electric sub panel must be properly grounded for operator safety Depending on length of run use wiring according to specification in wiring diagram and connect system to a separate UL listed breaker...

Page 9: ...90 degree connectors or other plumbing accessories For continuous optimal performance make sure suction and discharge lines are free of contamination nothing is blocking the flow of fuel and the sucti...

Page 10: ...OUR and MIN respectively to set desired start time for 1ON 4 Press TIMER to switch to 1OFF 5 Press DAY as often as required to select the same combinations of days as in step 2 must be consistent 6 Pr...

Page 11: ...will not eliminate the necessity to prime the complete system The system is primed through the primary filter as well as the suction line s have to be completely filled with fuel no trapped air prior...

Page 12: ...ust the Wrench Key turn at a time CCW to increase the vacuum alarm s set point 5 After adjusting the settings perform the testing procedure s for the switch es as outlined in the commissioning section...

Page 13: ...rator s Note All filter elements should be replaced at least every six 6 months Servicing the Primary Filter Water Separator Clogged filter elements restrict the flow of fuel resulting in the system s...

Page 14: ...Note Disposal of fuel associated waste and filters must be in accordance with all applicable federal state and local rules laws standards and regulations WARNING Some fuels may have been treated with...

Page 15: ...w filter element installed 1 Heavily contaminated fuel excessive water in tank 2 Restriction in plumbing on inlet side too high 3 Excessive lift 4 Inoperative foot valve 5 Inlet ball valve not fully o...

Page 16: ...limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by a...

Page 17: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Page 18: ...required part numbers and quantity The drawings parts list included in this manual are the most accurate source of part numbers for your FPS COMPACT Replacement Filter Elements Primary Filter Water S...

Reviews: