System Operation 

Apply control power to unit. Place breaker for the System Controller in the “ON” position.  

Pump Operation 

Automatic Mode: 

Press the ‘MANUAL’ button on the System Controller until ‘AUTO’ is indicated on the display. When the timer contacts 
close, the pump will start and run until the scheduled timer setting has expired. See the 

Controller

 section for setting the 

timer for scheduled run times. 
 

On Mode: 

Press the ‘MANUAL’ button on the System Controller until ‘ON’ is indicated on the display. The pump motor will run until 
the system is switched off, into “Auto” mode, or an alarm has been tripped.

 

Alarms 

Alarms featured on the system include:  

 

Leak Detection (system shutdown, alarm indication) 

o

 

Activated when the Float Switch in the system’s drip tray detects a raised liquid level. The system will go 
into an alarm state and the pump will not be allowed to be run until the alarm is addressed and cleared. 

 
Note: Disposal of fuel and associated waste should be done in accordance with Federal, State and Local regulations. 

 

 

High Vacuum (system shutdown, alarm indication) 

o

 

Activated when the Vacuum Switch, placed on the suction side of the pump set, detects a reading above 
the factory set point (12” HG). The system will go into an alarm state and the pump will not be allowed to 
run until the alarm is addressed and reset. 

 

High Water (system shutdown, alarm indication) 

o

 

Activated when water level trips the Water Detection Alarm Module via the Water Detection Sensor 
Probes located on the mechanical water separator. 

 
Once triggered alarms are addressed, each alarm can be reset via the System Controller. 

 

Summary of Contents for FPS Compact Series

Page 1: ...on Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com FPS FPS Compact Instruction Operating Maintenance Manual COMPACT FUEL MAINTENANCE SYSTEM REV030...

Page 2: ...REV0302COM010120 1...

Page 3: ...ly 8 Important Installation Precautions 8 Controller 9 Setting the Current Date and Time 9 Programming the Timer 9 Priming the System 10 Priming Procedure 10 Commissioning Initial Start Up 11 Gauge Ve...

Page 4: ...ose Barb System Back Plate Powder Coated Aluminum Operating Temperature 41 104 F 5 40 C Electrical 12VDC 10A or 24VDC 5A Pump DC Gear Pump Suction Capability Primed 10 ft 304 8 cm Total Dynamic Head T...

Page 5: ...tch Water Detection Alarm Module Vacuum Switch Leak Detection Float Switch Pump Motor DC Gear Pump Primary Filter Water Separator Fuel Filter o Standard issue back flushable 30 micron hydrophobic filt...

Page 6: ...tion o Activated when the Float Switch in the system s drip tray detects a raised liquid level The system will go into an alarm state and the pump will not be allowed to be run until the alarm is addr...

Page 7: ...ectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that could...

Page 8: ...r electric sub panel must be properly grounded for operator safety Depending on length of run use wiring according to specification in wiring diagram and connect system to a separate UL listed breaker...

Page 9: ...90 degree connectors or other plumbing accessories For continuous optimal performance make sure suction and discharge lines are free of contamination nothing is blocking the flow of fuel and the sucti...

Page 10: ...OUR and MIN respectively to set desired start time for 1ON 4 Press TIMER to switch to 1OFF 5 Press DAY as often as required to select the same combinations of days as in step 2 must be consistent 6 Pr...

Page 11: ...will not eliminate the necessity to prime the complete system The system is primed through the primary filter as well as the suction line s have to be completely filled with fuel no trapped air prior...

Page 12: ...ust the Wrench Key turn at a time CCW to increase the vacuum alarm s set point 5 After adjusting the settings perform the testing procedure s for the switch es as outlined in the commissioning section...

Page 13: ...rator s Note All filter elements should be replaced at least every six 6 months Servicing the Primary Filter Water Separator Clogged filter elements restrict the flow of fuel resulting in the system s...

Page 14: ...Note Disposal of fuel associated waste and filters must be in accordance with all applicable federal state and local rules laws standards and regulations WARNING Some fuels may have been treated with...

Page 15: ...w filter element installed 1 Heavily contaminated fuel excessive water in tank 2 Restriction in plumbing on inlet side too high 3 Excessive lift 4 Inoperative foot valve 5 Inlet ball valve not fully o...

Page 16: ...limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by a...

Page 17: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Page 18: ...required part numbers and quantity The drawings parts list included in this manual are the most accurate source of part numbers for your FPS COMPACT Replacement Filter Elements Primary Filter Water S...