AWG I Operating manual I Fittings I
Inductors Z2, Z4 and Z8
USE
M1061B10 I Rev. 01-02/20
ENGLISH
35 / 40
5. As soon as only clear water and no more extinguishing foam
emerges from the foam nozzle, close the hand lever. If necessary,
perform multiple rinsing passes.
6. Shut off the water supply and, by hand or with the use of a coupling
spanner, detach the input and output side couplings from the fixed
couplings.
Important
Water may emerge when the coupling is released.
5.3
Visual inspection after each use
The inductor is separated from the water supply.
The inductor must not be contaminated with foam agent. If neces-
sary, rinse the inductor again as described in the previous section.
1. Check the inductor and the pick tube (accessory) for visible damage.
Important
Do not continue to use damaged components!
If you discover any damage, this must be reported to
the person or department responsible.
6
FUNCTIONAL TEST
6.1 Prerequisites
All testing of the AWG Inductors Z2, Z4 and Z8 must be carried out in
accordance with the manufacturer's technical documentation and must
be documented if necessary.
The following inspections are defined for the inductors:
– Mandatory BASIC Inspection after each use
– Mandatory STANDARD Inspection every 12 months
– Optional ADVANCED Inspection every 12 months
The STANDARD and ADVANCED inspections may only be carried out
by qualified personnel who have been trained for these inspections:
– Firefighters who have received training as firefighting equipment
maintenance technicians or persons with equivalent qualifications
– Or, if desired, directly by the manufacturer