background image

AV6A 14

Profinet IO “N” 

Profinet IO is typically a master/slave network-the master/scanner 

device gathers data from each (slave) device on the bus.  Avtron 

encoders are Profinet IO slave devices.  Profinet IO commands 

include a subset of Profidrive commands-these commands are also 

supported by Avtron encoders.  Avtron encoders support RT (real 

time) and IRT (isochronous real time) functions. 

Profinet IO may be wired in several different configurations, but 

the best known is a “star” configuration where each device has a 

“home-run” network cable that connects to a central switch or hub.  

To reduce the cabling requirements, Avtron encoders support 

“daisy-chain” configurations.  The master device must be at one end 

of the bus or connected to a hub or switch.  The input signal from 

the master or switch is repeated by each encoder to its output port 

(labelled “Port 2”), which can in turn be connected to an input Port 

1 of another encoder.  No external or switched termination resistors 

are required for Profinet IO.  Power is carried to the device via a 

separate set of wires.  A maximum of (7) encoders can be daisy-

chained together to a single EtherNet/IP master/scanner or switch 

port.

Preferred cable:  Nidec Avtron recommends structured Ethernet 

wiring systems, available from a broad range of vendors as well as 

Avtron.  

For more details on Profinet, consult the Profibus Users Association 

(PI):

http://www.profibus.com/

Number of 

Nodes

1-7

Units

Max. Overall 

Cable Length*

330 

[100]

ft 

[m]

*Using Ethernet standard cable, CAT6 or CAT5e required

Setting Station/Node, Baud Rate, Duplex

NOTE:  There is no hardware method to set the Station/Node number 

(IP address) for Avtron EtherNet/IP address.

Setting IP Address via STEP7 (Siemens) software:

Begin with a factory-default encoder.  Make a physical Ethernet 

connection between a PC and the encoder.  Run the STEP7 

software.  Under menu item PLC->Ethernet->Edit Ethernet Mode-

>Browse.  STEP7 will produce a list of all encoders via MAC-

address.  Optional:  use the flash LED button to cause the LED 

to flash to verify communication with the encoder.  Select menu 

item Use IP Parameters, enter the IP address then->Assign IP 

Configuration.  Enter the device name.  Any IP address from 0.0.0.0 

to 223.255.255.255 (excluding 127.x.x.x) is permitted.

Cycle power.

The encoder should now operate at the assigned IP address, 

which can be validated using the ping command from the PC.  The 

assigned name can be used throughout STEP7 software to address 

the encoder.

Note that if more than one encoder is to be used on the same 

Profinet IO network, each encoder must be assigned a unique name, 

and individual encoders must be connected one-by-one to assign 

names using STEP7 software during setup.

Ethernet baud rate and duplex are auto-detected by the encoder, no 

settings are required. 100mBit and 10mBit are supported, Gigabit 

Ethernet is not supported at the encoder level but may be utilized at 

the switch backbone level.  Consult Nidec Avtron if manual forcing of 

duplex is required.

Measuring Position, Speed, and Acceleration

Avtron encoders support three modes of operation:

Standard

Profile (Profidrive) 4.0 (supports DP-V2 commands)

Profile (Profidrive) 4.1 (supports DP-V2 commands)

Profile 4.0 and 4.1 require a special GSDML file, contact factory.

To read position and speed into your device (acceleration 

measurement is not supported directly):  

Following the instructions for your master/scanner module for 

the Profinet IO network, load the encoder GSDML file into your 

configuration.  Assign it to the correct IP address node number.  

Store the configuration to the scanner module.

All of the position data and other parameters will be read by 

the scanner module and placed in registers identified in the 

configuration package.

Cyclic Data

ID 

(dec)

Function

Type

Notes

3

Master 

heartbeat

UINT

4

Slave 

heartbeat

UINT

6

Velocity

INT

 

8

Velocity

DINT

9

Ctl Word 

UINT

bit 11=preset/zero

bit 12=capture position

bit 13=enable cyclic xmit

bit 14=disable error xmit

bit 15=clear errors

10

Status

UINT

Bit 12=ack capture position

Bit 13=ack cyclic xmit req

Bit 14=ack disable error

Bit 15=encoder error

11

Position 1*

DINT

12

Position 2*

DINT

If encoder error (bit 15, 

ID10), error message output 

to Position 2 instead of 

position.

39

Position 3

DINTx2 right-aligned

19

Vel. Update

EUINT

0=1sec, 1=0.1s, 2=0.01s, 

3=RPM

29

Status

BYTE

2A

Units per 

span

UDINT

read only, set w/0x10

2B

# Spans

UINT

# revolutions

33

Offset

DINT

Poffset

64

Device Type DINT

0x22 = Encoder

65

Rollover

DINT

0=off, 1=on, 2=auto

66

Vel’cty Filter DINT

0=low pass, 1=mid, 2=off

* Depending on the mode of operation selected, the position data is 

aligned differently, but always presented little-Endian (right most bit 

is least significant):

Standard Profile:  data is right-justified:  Single-turn data/data within 

Summary of Contents for AV6A Series

Page 1: ...tion Supplied AV6A Encoder Optional none Not Supplied Open Wrenches Hex Wrenches Dial Indicator Gauge Caliper Gauge Coupling Foot Mount and Mounting Screws AV6A PART NUMBERS AND AVAILABLE OPTIONS Mode...

Page 2: ...cceptable loosen the mounting screws to the flange and apply thin metal shims to the face of the encoder and retest the angular alignment until acceptable 5a Remove the AV6A Transfer punch or layout t...

Page 3: ...e encoder replies Transmission rates vary but these messages can be extremely short and typically require scope triggering to spot them For CANOpen ensure termination resistors are in place or switche...

Page 4: ...84 12 or 14 bits F Line Driver Specs See table G Connectors See connector options on page 1 H Accuracy 0 04 deg 2 6 arc min 12 bit units 0 02 deg 1 3 arc min 16 bit units MECHANICAL A Shaft Inertia 0...

Page 5: ...encoder is reset typically power cycled Power Up Sequence The encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 nn node number typically 0x01 for units wit...

Page 6: ...SDO object 0x2300 Example encoder at node 20 store changes ID 0x620 0x22 0x00 0x23 0x00 0x55 0xAA 0xAA 0x55 No reset is triggered Cycle power after saving changes to parameters Other Parameters Contac...

Page 7: ...cycled before the values are stored the encoder will default to the values previously stored in EEPROM Setting Node Number To set the node number on units with a connection cap Set the address using t...

Page 8: ...cabling system and that no termination resistors are in placed or activated in the middle of the system Remove the connections to the master controller and all devices or power down all devices Measur...

Page 9: ...an lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided directly above the single turn data bitwise Example 12 turns x 13...

Page 10: ...rs encoder operational LS DA 1 Status Flashing Green Active inbound communication LS DA 2 Status Green Output connected to next encoder LS DA 2 Flashing Green Active communication to next encoder Erro...

Page 11: ...turns position data Zero Position for Multiturn Encoders Single turn Encoders NOTE Do not attempt to use zero preset function while the encoder is rotating Doing so will produce unpredictable results...

Page 12: ...tion Speed and Acceleration To read position into your device acceleration and speed measurement is not supported For multiturn single turn encoders position data provided as 4 bytes 32 bits Format is...

Page 13: ...ed to each cable Use hubs or switches to connect multiple Modbus TCP encoders to the master device A software snoop or sniffer program can also be used to packet analyze the communication If the posit...

Page 14: ...ow operate at the assigned IP address which can be validated using the ping command from the PC The assigned name can be used throughout STEP7 software to address the encoder Note that if more than on...

Page 15: ...coder use the parameters supplied in the GSDML file to set the appropriate mode Store the resulting configuration into the scanner module Storing Saving Encoder Parameters to EEPROM To store the curre...

Page 16: ...laced in registers identified in the configuration package Profibus DP Diagnostic LEDs LED Status Meaning STATUS ERROR Green Off Power Ok Status OK STATUS ERROR Green Red No Configuration Data Receive...

Page 17: ...s required Measuring Position Speed and Acceleration To read position and speed into your device acceleration measurement is not supported Following the instructions for your master scanner module for...

Page 18: ...unication A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Preset parameter may...

Page 19: ...Upon the Set Zero signal returning to logic zero falling edge the encoder count value will be set to zero Set Direction input 10K resistance For input logic zero or no connection the encoder will cou...

Page 20: ...st L GND 0V BROWN 3 NC PINK NC BLUE NC GRAY CAN_H Rightmost H CAN_L Rightmost L CAN_GND Rightmost G Double up Double up REF SIGNAL CAN_GND V CAN_H CAN_L GND 0V Optional Daisy Chain CAN_H CAN_L CAN_GND...

Page 21: ...ftmost H CAN_L BLUE 3 Leftmost L NC NC NC CAN_H Rightmost H CAN_L Rightmost L Double up Double up REF SIGNAL V V GND CAN_H CAN_L Optional Daisy Chain CAN_H CAN_L GND V DeviceNet Bus D AV6A WIRING DIAG...

Page 22: ...ey pairing as shown optional overall shield may be used for high noise environments NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a...

Page 23: ...W BROWN 16 BIT 15 WHITE YELLOW 15 BIT 14 BROWN GREEN 14 BIT 13 WHITE GREEN 13 BIT 12 BLUE RED 12 BIT 11 GREY PINK 11 BIT 10 VIOLET 10 BIT 9 BLACK 9 BIT 8 RED 8 BIT 7 BLUE 7 BIT 6 PINK 6 BIT 5 GREY 5 B...

Page 24: ...OWN GREEN NC NC 14 BIT 13 WHITE GREEN NC 13 13 BIT 12 BLUE RED 12 12 12 BIT 11 GREY PINK 11 11 11 BIT 10 VIOLET 10 10 10 BIT 9 BLACK 9 9 9 BIT 8 RED 8 8 8 BIT 7 BLUE 7 7 7 BIT 6 PINK 6 6 6 BIT 5 GREY...

Page 25: ...own optional overall shield may be used for high noise environments Communication Bus M Modbus TCP Pinout AV6A WIRING DIAGRAMS Master Scanner or Switch Power Supply NOTE For encoder switch connections...

Page 26: ...B Bus A out 5 pin female 2 Rightmost A Bus B out 4 Rightmost B REF SIGNAL GND OV Vs Bus A out Bus B out Bus A in Bus B in NOTE Profibus cabling required Obey pairing as shown If termination resistor R...

Page 27: ...NK 4 6 SET ZERO BLUE 9 7 SET DIRECTION RED 8 8 NC 5 NC 6 NC 7 NC 10 REF SIGNAL GND Vs CLK CLK DAT DAT SET ZERO SET DIRECTION NC NC NC NC NOTE Twisted pair cable required with overall shield individual...

Page 28: ...or M12 K Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed t...

Page 29: ...12 E Axial exit E Multiturn IP65 Seals and Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to...

Page 30: ...M27 G End Axial exit E Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed...

Page 31: ...R Connector M12x3 Side Exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superi...

Page 32: ...M12 8 E Side exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to c...

Page 33: ...5 1 25 pilot Devicenet D Connector 2xM12 5 B Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A DIMENSIONS IN INCHES MILLIMETERS ALL DIMENSIONS ARE APPROXIMATE Features and specifications...

Reviews: