Current Loop 1 & 2 (RMA-CL1-SEN & RMA-CL2-SEN)

Early versions of the Room Alert 12E have this polarity reversed: LEFT = negative (-), 

and RIGHT = positive (+). If you observe your voltage value flipping back and forth 

from “0” to “5,” it’s likely that the speaker wires simply need to be inserted in the 

opposite contact.

Room Alert models 32E and 12E have built-in analog input ports; Room Alert models 32E, 

24E, 12E, 4E & 3E can also interface with analog sensors through AVTECH’s Temperature 

& Analog Sensor, which connects to Room Alert’s Digital Port. For more information 

about AVTECH’s Temperature & Analog Sensor, please see its Installation Note, visit        

AVTECH.com

 or contact a Product Specialist.

Sensor Features & Specifications

Environment Condition Monitored

Electrical current (amps)

Type Of Sensor

Analog

Power Supply

Induced from monitored conductor

Sensor Cable Type

Low-voltage 2-wire speaker cable

Included

Yes

Length

25'

Maximum Extendible Length

100'

Output Voltage

0 to 5 VDC

Input Amperage Range

Current Loop 1 (RMA-CL1-SEN)

0 to 50 A

Current Loop 2 (RMA-CL2-SEN)

0 to 250 A

Accuracy

+/- 1.0% (2 to 100% FSO)

Response Time

< 100 mS

Operating Frequency Range

50 to 600 Hz

Isolation Voltage

2,200 VAC

Maximum Sensing Current Voltage

600 VAC

Apeture (Hole) Size

0.75" (Accepts cables up to 350 MCM)

DIN Rail Size

35 mm

Operating Temperature

-15 to 40º C (5 to 104º F)

Operating Humdity

0 to 95% RH, non-condensing

Enclosure Rating

UL94-5VB

Compatible Products

Room Alert 32E/W & 12E

     

Through the built-in Analog Input Port(s),

Room Alert 32E/W, 24E, 12E, 4E & 3E

     

With a Temperature & Analog Sensor

AVT-171211-3.1.0

Summary of Contents for RMA-CL1-SEN

Page 1: ...ce device being monitored for the most accurate readings Current Loop 1 Current Loop 2 High H 0 to 50 A Middle M 0 to 20 A Low L 0 to 10 A H 0 50A M 0 20A L 0 10A 0 5 VDC COM H M L Use Insulated Conductors Only High H 0 to 250 A Middle M 0 to 200 A Low L 0 to 100 A H 0 250A M 0 200A L 0 100A 0 5 VDC COM H M L Use Insulated Conductors Only To change the setting pull the jumper up to detach it from ...

Page 2: ...or the Current Loop to operate correctly 5 Lock the Current Loop closed by pressing the cover down firmly and listening for the click Step 3 Connect your Current Loop to Room Alert Do not connect the analog inputs on AVTECH products to live circuits of over 5 VDC Use only low voltage 2 wire cable to connect analog inputs Your Current Loop comes with one end of the 25 speaker wire already attached ...

Page 3: ... Features Specifications Environment Condition Monitored Electrical current amps Type Of Sensor Analog Power Supply Induced from monitored conductor Sensor Cable Type Low voltage 2 wire speaker cable Included Yes Length 25 Maximum Extendible Length 100 Output Voltage 0 to 5 VDC Input Amperage Range Current Loop 1 RMA CL1 SEN 0 to 50 A Current Loop 2 RMA CL2 SEN 0 to 250 A Accuracy 1 0 2 to 100 FSO...

Page 4: ... Scroll to your external digital sensor s and find the digital sensor you connected your Temperature Analog Sensor to 2 Enable the sensor by selecting Enabled next to the High Low Adjust fields The built in analog sensor will not appear in the Room Alert web interface Device ManageR your RoomAlert com account or SNMP program unless it is enabled 2 Select Temp Analog from the Sensor Type drop down ...

Page 5: ... Sensor Label you may leave the default Analog Sensor X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods In High and Low you may leave the default 0 which means no alarm is configured or enter values for high and low thresholds These values must be within the range you entered i...

Page 6: ...e Temperature Sensors If you ordered a customized version please use your custom Reference and Scale instead of these values Standard Extreme Low Temperature Sensor Conversion To Fahrenheit Conversion To Celsius High Low High Low Reference 5 1 Reference 5 1 Scale 32 328 Scale 0 200 Units F Units C Standard Extreme High Temperature Sensor Conversion To Fahrenheit Conversion To Celsius High Low High...

Reviews: