Page 2 

Current Loop 1 & 2 (RMA-CL1-SEN & RMA-CL2-SEN)

screws or snap it directly on to a 35 mm DIN rail. 

Leave a minimum of 1" between the Current Loop and any other magnetic device(s).

Step 2: Insert a single insulated conductor into your Current Loop.

1.  Disconnect power to the insulated cord that you intend to monitor.

2.  Open the Current Loop by either prying 

open the latch with a flat-tip screw driver 

or pressing down on the two side tabs 

with your fingers to release the cover. 

3.  Wrap the Current Loop around a single 

insulated conductor. Examples are shown 

here.

4.  Before you close the Current Loop, check 

the surfaces of the magnetic core to be 

sure they’re clear. They need good contact 

for the Current Loop to operate correctly.

5.  Lock the Current Loop closed by pressing the cover down firmly and listening for the 

click.

Step 3: Connect your Current Loop to Room Alert.

Do not connect the analog inputs on AVTECH products to live circuits of over 5 VDC.
Use only low-voltage 2-wire cable to connect analog inputs.

Your Current Loop comes with one end of the 25' speaker wire 

already attached to its + / - contacts. 

Follow these steps to attach the other end of the 25' speaker 

wire to the input ports on your built-in or external Room Alert 

Analog Sensor:

1.  Separate and strip the free ends of the speaker wire. Expose 

about ¼" of wire.

2.  Look at the + / - contacts on the Current Loop and note which 

wire is attached to each contact. 

3.  Insert the negative (-) wire into the RIGHT (-) contact of the 

Analog Sensor Input port.

4.  Insert the positive (+) wire into the LEFT (+) contact of the Analog Sensor Input port.

Summary of Contents for RMA-CL1-SEN

Page 1: ...ce device being monitored for the most accurate readings Current Loop 1 Current Loop 2 High H 0 to 50 A Middle M 0 to 20 A Low L 0 to 10 A H 0 50A M 0 20A L 0 10A 0 5 VDC COM H M L Use Insulated Conductors Only High H 0 to 250 A Middle M 0 to 200 A Low L 0 to 100 A H 0 250A M 0 200A L 0 100A 0 5 VDC COM H M L Use Insulated Conductors Only To change the setting pull the jumper up to detach it from ...

Page 2: ...or the Current Loop to operate correctly 5 Lock the Current Loop closed by pressing the cover down firmly and listening for the click Step 3 Connect your Current Loop to Room Alert Do not connect the analog inputs on AVTECH products to live circuits of over 5 VDC Use only low voltage 2 wire cable to connect analog inputs Your Current Loop comes with one end of the 25 speaker wire already attached ...

Page 3: ... Features Specifications Environment Condition Monitored Electrical current amps Type Of Sensor Analog Power Supply Induced from monitored conductor Sensor Cable Type Low voltage 2 wire speaker cable Included Yes Length 25 Maximum Extendible Length 100 Output Voltage 0 to 5 VDC Input Amperage Range Current Loop 1 RMA CL1 SEN 0 to 50 A Current Loop 2 RMA CL2 SEN 0 to 250 A Accuracy 1 0 2 to 100 FSO...

Page 4: ... Scroll to your external digital sensor s and find the digital sensor you connected your Temperature Analog Sensor to 2 Enable the sensor by selecting Enabled next to the High Low Adjust fields The built in analog sensor will not appear in the Room Alert web interface Device ManageR your RoomAlert com account or SNMP program unless it is enabled 2 Select Temp Analog from the Sensor Type drop down ...

Page 5: ... Sensor Label you may leave the default Analog Sensor X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods In High and Low you may leave the default 0 which means no alarm is configured or enter values for high and low thresholds These values must be within the range you entered i...

Page 6: ...e Temperature Sensors If you ordered a customized version please use your custom Reference and Scale instead of these values Standard Extreme Low Temperature Sensor Conversion To Fahrenheit Conversion To Celsius High Low High Low Reference 5 1 Reference 5 1 Scale 32 328 Scale 0 200 Units F Units C Standard Extreme High Temperature Sensor Conversion To Fahrenheit Conversion To Celsius High Low High...

Reviews: