OM-ECOARCH 9
Installation Instructions
Install Power
Locate the relay box on top of the hood. Inside the relay box locate terminal strip 1 (TS-1).
On terminal strip 1 connect a 115/60/1 – 20 amp service to terminals 1 and 2. THE 120V
POWER SOURCE CONNECTED TO THE RELAY BOX IS FOR THE HOOD CONTROL SYSTEM
AND UV LIGHTS ONLY. THIS POWER SOURCE IS NOT FOR THE CANOPY LIGHTS OR FANS.
Those systems require separate power sources.
Control Panel
The control panel will be mounted on the hood or remotely. If the control panel is mounted
on the hood no installation is required. If the control panel is located remotely then
installation is required.
Remote Located Control
• Locate terminal strip 2 (TS-2) in relay box located on top of the hood. This is where
the UV light switch will terminate. THE POWER AT (TS-2) IS 115V/1/60. Connect one
side of the switch to terminal 1 and the other side of the switch to terminal 2. Please
make sure the switch is connected to ground.
UV ELECTRICAL
DANGER!
UV LIGHT BULBS GIVE OFF ULTRA VIOLET
LIGHT WHICH CAN BURN YOUR EYES.
ALWAYS USE CAUTION WHEN SERVICING
THE UV SYSTEM.
DANGER!
PLEASE USE CAUTION WHEN INSTALLING
OR SERVICING THE ELECTRICAL SYSTEM
FOR THE UV HOOD. ELECTRICAL SHOCK CAN
CAUSE SERIOUS INJURY OR EVEN DEATH!!!
ELECTRICAL WORK SHOULD ONLY BE DONE
BY QUALIFIED PERSONNEL.
PLEASE ADHERE TO ALL ELECTRICAL
NATIONAL, STATE, AND LOCAL CODES.
Summary of Contents for ecoarch
Page 7: ...OM ECOARCH 7 Installation Instructions Figure 5...
Page 8: ...8 OM ECOARCH Installation Instructions Figure 5 Continued...
Page 10: ...10 OM ECOARCH Installation Instructions Figure 6a RELAY BOX BALLAST BOX...
Page 11: ...OM ECOARCH 11 Installation Instructions Figure 6b...
Page 12: ...12 OM ECOARCH Installation Instructions Figure 6c...
Page 15: ...OM ECOARCH 15 Installation Instructions Figure 7 FOR CONTROL PANEL IF PROVIDED...