background image

7

detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)

shall not be used.

6 LEAK DETECTION METHODS

The following leak detection methods are deemed acceptable for systems containing

flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants,

but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be

calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of

ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a

percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and

the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are

suitable for use with most refrigerants but the use of detergents containing chlorine shall be

avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak

is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found

which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by

means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN)

shall then be purged through the system both before and during the brazing process.

7 REMOVAL AND EVACUATION

When breaking into the refrigerant circuit to make repairs – or for any other purpose – con-

ventional procedures shall be used.However, it is important that best practice is followed

since flammability is a consideration. The following procedure shall be adhered to: remove

refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit

by cutting or brazing.The refrigerant charge shall be recovered into the correct recovery cylinders.

The system shall be “flushed” with OFN to render the unit safe. This process may need to be

repeated several times.Compressed air or oxygen shall not be used for this task. Flushing shall

be achieved by breaking the vacuum in the system with OFN and continuing to fill until the

working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum.

This process shall be repeated until no refrigerant is within the system. When the final OFN

charge is used, the system shall be vented down to atmospheric pressure to enable work to take

place.This operation is absolutely vital if brazing operations on the pipework are to take place.

Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is

ventilation available.

8 CHARGING PROCEDURES

In addition to conventional charging procedures,the following requirements shall be followed.

- Ensure that contamination of different refrigerants does not occur when using charging

equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant

contained in them.

- Cylinders shall be kept upright.

- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

- Label the system when charging is complete (if not already).

- Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak

tested on completion of charging but prior to commissioning. A follow up leak test shall be

carried out prior to leaving the site.

9 DECOMMISSIONING

Before carrying out this procedure, it is essential that the technician is completely familiar

with the equipment and all its detail. It is recommended good practice that all refrigerants are

Summary of Contents for A007E-10C

Page 1: ...Portable Air conditioner User s Manual R290 For Model A007E 10C Please read this user s manual carefully to ensure proper use maintenance and installation...

Page 2: ...me of Parts 12 3 Accessories 12 4 Appearance and Function of Control Panel 13 5 Appearance and Function of Remote Control 14 6 Operation Introduction 15 7 Installation Explanations 17 8 Maintenance Ex...

Page 3: ...urces for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware the refrigerants may not contain an odour Appliance shall be installed operated...

Page 4: ...n accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry Repairs must be performed based on the recommen...

Page 5: ...ldren shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision 13 The appliance shall be installed in accordance with national wiring regulatio...

Page 6: ...nder the supervision of the person competent in the use of flammable refrigerants 22 Do not operate or stop the unit by inserting or pulling out Die power plug it may cause electric shock or fire due...

Page 7: ...der or CO 2 fire extinguisher adjacent to the charging area 1 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contain...

Page 8: ...to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation...

Page 9: ...with inert gas open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushed with OFN to render the unit safe This pr...

Page 10: ...bel shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 11 RECOVERY When removing refrigerant from a system either for servicin...

Page 11: ...that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is opened Ventilated enclosure see Clause GG 4 Safety of the appliance depend...

Page 12: ...before putting into service d Decommissioning If the safety is affected when the equipment is putted out of service the refrigerant charge shall be removed before decommissioning Ensure sufficient ve...

Page 13: ...All required signs are to be maintained and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions...

Page 14: ...Power cord 2 Front panel 6 Drainage outlet 3 Louver 7 Air inlet 4 Castor 8 Air outlet 3 Accessories Part Description Quantity Exhaust hose 1 Window Connector 1 Housing adaptor 1 Remote Controller 1 2...

Page 15: ...optional After unpacking please check whether the above mentioned accessories are included and check their purposes in the installation introduction in this manual 4 Appearance and Function of Contro...

Page 16: ...on off 6 Dehumidifying G Signal receiver 7 Fan A Power on off 1 Water full B Temperature up 2 High fan speed C Temperature down 3 Low fan speed D Operation MODE 4 Timer on off E Fan speed 5 Cooling F...

Page 17: ...rby 2 As shown in Fig 2 and Fig 2a install the exhaust hose and adjust the window position well Fig 2 Fig 2a 3 As shown in Fig 6 connect drain hose well only for using heating model 4 Insert the power...

Page 18: ...le for a cold single unit Press the Mode button till the Heat icon appears Press the or button to select a desired room temperature 16 31 Press the Fan Speed button to select wind speed 6 Timer operat...

Page 19: ...rain hose to the bottom drain hole Fig 6 the unit can also work well If splash motor is damaged intermittent drainage can also be used Under this condition when the water full indicator lights up plea...

Page 20: ...Fig 4 B Window Kit Installation The installation manner of window slider kit is mostly in horizontal or vertical As shown Fig 5 and Fig 5a check the min and max size of the window before the installat...

Page 21: ...r level safety switches it controls water level When water level reaches an anticipated height the water full indicator lamp lights up If water splash motor is damaged when the water is full please re...

Page 22: ...clogged with dust dirt the air filter should be cleaned once every two weeks Dismounting Open the air inlet grille and take off air filter Cleaning Clean the air filter with neural detergent in lukew...

Page 23: ...Connect or clean the exhaust air hose Temperature setting is too high Reset the temperature Air inlet is blocked Clean the air inlet 3 Noisy The ground is not level or not flat enough Place the unit o...

Reviews: