background image

10

Check safety equipment before putting into service.

c) Repair

Portable equipment shall be repaired outside or in a workshop specially equipped for

servicing units with flammable refrigerants.

Ensure sufficient ventilation at the repair place.

Be aware that malfunction of the equipment may be caused by refrigerant loss and a

refrigerant leak is possible.

Discharge capacitors in a way that won’t cause any spark.

When brazing is required, the following procedures shall be carried out in the right

order:

– Remove the refrigerant. If the recovery is not required by national regulations, drain

the refrigerant to the outside. Take care that the drained refrigerant will not cause

any danger. In doubt, one person should guard the outlet. Take special care that

drained refrigerant will not float back into the building.

– Evacuate the refrigerant circuit.

– Purge the refrigerant circuit with nitrogen for 5 min.

– Evacuate again.

– Remove parts to be replaced by cutting, not by flame.

– Purge the braze point with nitrogen during the brazing procedure.

– Carry out a leak test before charging with refrigerant.

Reassemble sealed enclosures accurately. If seals are worn, replace them.

Check safety equipment before putting into service.

d) Decommissioning

If the safety is affected when the equipment is putted out of service, the refrigerant

charge shall be removed before decommissioning.

Ensure sufficient ventilation at the equipment location.

Be aware that malfunction of the equipment may be caused by refrigerant loss and a

refrigerant leak is possible.

Discharge capacitors in a way that won’t cause any spark.

Remove the refrigerant. If the recovery is not required by national regulations, drain

the refrigerant to the outside. Take care that the drained refrigerant will not cause any

danger. In doubt, one person should guard the outlet. Take special care that drained

refrigerant will not float back into the building.

Evacuate the refrigerant circuit.

Purge the refrigerant circuit with nitrogen for 5 min.

Evacuate again.

Fill with nitrogen up to atmospheric pressure.

Put a label on the equipment that the refrigerant is removed.

e) Disposal

Ensure sufficient ventilation at the working place.

Remove the refrigerant. If the recovery is not required by national regulations, drain

the refrigerant to the outside. Take care that the drained refrigerant will not cause any

danger. In doubt, one person should guard the outlet. Take special care that drained

refrigerant will not float back into the building.

Evacuate the refrigerant circuit.

Purge the refrigerant circuit with nitrogen for 5 min.

Summary of Contents for A007E-10C

Page 1: ...Portable Air conditioner User s Manual R290 For Model A007E 10C Please read this user s manual carefully to ensure proper use maintenance and installation...

Page 2: ...me of Parts 12 3 Accessories 12 4 Appearance and Function of Control Panel 13 5 Appearance and Function of Remote Control 14 6 Operation Introduction 15 7 Installation Explanations 17 8 Maintenance Ex...

Page 3: ...urces for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware the refrigerants may not contain an odour Appliance shall be installed operated...

Page 4: ...n accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry Repairs must be performed based on the recommen...

Page 5: ...ldren shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision 13 The appliance shall be installed in accordance with national wiring regulatio...

Page 6: ...nder the supervision of the person competent in the use of flammable refrigerants 22 Do not operate or stop the unit by inserting or pulling out Die power plug it may cause electric shock or fire due...

Page 7: ...der or CO 2 fire extinguisher adjacent to the charging area 1 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contain...

Page 8: ...to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation...

Page 9: ...with inert gas open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushed with OFN to render the unit safe This pr...

Page 10: ...bel shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 11 RECOVERY When removing refrigerant from a system either for servicin...

Page 11: ...that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is opened Ventilated enclosure see Clause GG 4 Safety of the appliance depend...

Page 12: ...before putting into service d Decommissioning If the safety is affected when the equipment is putted out of service the refrigerant charge shall be removed before decommissioning Ensure sufficient ve...

Page 13: ...All required signs are to be maintained and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions...

Page 14: ...Power cord 2 Front panel 6 Drainage outlet 3 Louver 7 Air inlet 4 Castor 8 Air outlet 3 Accessories Part Description Quantity Exhaust hose 1 Window Connector 1 Housing adaptor 1 Remote Controller 1 2...

Page 15: ...optional After unpacking please check whether the above mentioned accessories are included and check their purposes in the installation introduction in this manual 4 Appearance and Function of Contro...

Page 16: ...on off 6 Dehumidifying G Signal receiver 7 Fan A Power on off 1 Water full B Temperature up 2 High fan speed C Temperature down 3 Low fan speed D Operation MODE 4 Timer on off E Fan speed 5 Cooling F...

Page 17: ...rby 2 As shown in Fig 2 and Fig 2a install the exhaust hose and adjust the window position well Fig 2 Fig 2a 3 As shown in Fig 6 connect drain hose well only for using heating model 4 Insert the power...

Page 18: ...le for a cold single unit Press the Mode button till the Heat icon appears Press the or button to select a desired room temperature 16 31 Press the Fan Speed button to select wind speed 6 Timer operat...

Page 19: ...rain hose to the bottom drain hole Fig 6 the unit can also work well If splash motor is damaged intermittent drainage can also be used Under this condition when the water full indicator lights up plea...

Page 20: ...Fig 4 B Window Kit Installation The installation manner of window slider kit is mostly in horizontal or vertical As shown Fig 5 and Fig 5a check the min and max size of the window before the installat...

Page 21: ...r level safety switches it controls water level When water level reaches an anticipated height the water full indicator lamp lights up If water splash motor is damaged when the water is full please re...

Page 22: ...clogged with dust dirt the air filter should be cleaned once every two weeks Dismounting Open the air inlet grille and take off air filter Cleaning Clean the air filter with neural detergent in lukew...

Page 23: ...Connect or clean the exhaust air hose Temperature setting is too high Reset the temperature Air inlet is blocked Clean the air inlet 3 Noisy The ground is not level or not flat enough Place the unit o...

Reviews: