Configure and Wire Power
Do the following for each V100 in order for the ACM Embedded Controller application to not show an alarm:
1. Place a jumper across and - (22AWG).
2. Place a jumper across AC Fail + and - (22AWG).
3. Place a jumper across Batt Fail + and - (22AWG).
4. Connect the 12VDC +/- to the D8P board (18AWG), as noted below:
l
Connect the Addr 0 V100 12VDC + to Out2+ and - to Out2-.
l
Connect the Addr 1 V100 12VDC + to Out3+ and - to Out3-.
l
Connect the Addr 2 V100 12VDC + to Out4+ and - to Out4-.
l
Connect the Addr 3 V100 12VDC + to Out5+ and - to Out5-.
V100
(Addr 0)
Tamper
(Input 5)
+
-
+
+
-
-
-
+
AC
Fail
(Input 6)
Batt
Fail
(Input 7)
+12VDC
IN
V100
(Addr 3)
Tamper
(Input 5)
+
-
+
+
-
-
-
+
AC
Fail
(Input 6)
Batt
Fail
(Input 7)
+12VDC
IN
V100
(Addr 2)
Tamper
(Input 5)
+
-
+
+
-
-
-
+
AC
Fail
(Input 6)
Batt
Fail
(Input 7)
+12VDC
IN
V100
(Addr 1)
Tamper
(Input 5)
+
-
+
+
-
-
-
+
AC
Fail
(Input 6)
Batt
Fail
(Input 7)
+12VDC
IN
D8
OUT
8
7
6
5
4
3
2
1
+
+
-
-
-
-
-
-
-
-
+
+
+
+
+
+
+
+
Note
: For the steps below ensure that the card reader, door monitor (if available), request-to-exit (if
available) and lock wiring from the door are fed into the power supply enclosure and route to the
corresponding port on each V100 as desired.
5. If request-to-exit inputs from the door are available, connect them appropriately to the P2\REX and
P5\REX. (Refer to the appropriate Request-to-Exit device manual.)
Configure and Wire Power
19