FXT 5000 Series Installation Guide
2.2 Power and Thermal Specifications
FXT 5000 Series nodes use variable speed fans, so power depends on temperature. Maximum fan speeds are unlikely
to occur even at the highest specified ambient temperature (35° C/95° F). Power and thermal specifications are for a
system using 1+1 redundant power supplies, both supplying power.
2.2.1 FXT Series Nameplate Ratings
Nameplate Ratings for FXT 5000 Series Models
100 - 240 V ac
60 - 50 Hz
9.5 - 4.5 A
2.2.2 FXT 5850 Power and Thermal Measurements
FXT 5850 power at room temperature or at maximum fan speed
FXT 5850
At 22° C (71.6° F) Inlet Temperature
At Maximum Fan Speeds
Voltage (V)
100
120
208
230
240
100
120
208
230
240
Frequency (Hz)
60
60
60
50
50
60
60
60
50
50
Current (A)
2.89
2.39
1.41
1.29
1.24
3.57
2.94
1.73
1.57
1.51
Apparent Power (VA)
289
287
293
297
298
357
353
360
361
362
Power Factor
0.99
0.99
0.95
0.95
0.95
0.99
0.99
0.96
0.96
0.96
Real Power (W)
286
284
279
282
283
353
349
345
347
348
Thermal Dissipation
(BTU/Hr)
976
969
951
962
965
1206
1192
1179
1183
1187
2.2.3 FXT 5600 Power and Thermal Measurements
FXT 5600 power at room temperature or at maximum fan speed
FXT 5600
At 22° C (71.6° F) Inlet Temperature
At Maximum Fan Speeds
Voltage (V)
100
120
208
230
240
100
120
208
230
240
Frequency (Hz)
60
60
60
50
50
60
60
60
50
50
Current (A)
2.56
2.12
1.30
1.17
1.12
3.29
2.73
1.63
1.46
1.41
Apparent Power (VA)
256
255
270
269
268
329
328
339
336
338
Power Factor
0.99
0.99
0.94
0.93
0.93
0.99
0.99
0.96
0.96
0.95
Real Power (W)
254
252
253
250
249
326
324
325
322
321
Thermal Dissipation
(BTU/Hr)
866
861
865
854
851
1111
1107
1111
1100
1097
4