INSTALLATION
GB
5
Visit our website at Emerson.com/AVENTICS
1) The valve must only be supplied with 24V DC ±10% and a max. ripple of 10% (no supply via diode bridge). Overvolt-
age or a ripple rate exceeding these tolerances can damage the electronics.
2) The max. current at the digital output is 200 mA/4.8W (PNP output). The output is protected against short circuit
and overload.
3) If a relay (inductive load) is connected to the pressure switch output, a freewheel diode or a varistor must be used.
4) A shielded cable must be used for protection against interference and EMC.
5) The valve housing must be connected to the ground potential with low resistance via the ground connection (ØM4).
The eyelet of the grounding cable must be inserted between two toothed washers and fastened with a screw (M4).
The tightening torque corresponding to the screw must be observed.
2.
ELECTRICAL CONNECTION
CONNECTOR PINNING / CABLE WIRING
1
2
3
5
4
5-pin M12 female connector
250 Ohm
at current
setpoint
Valve
M12 connector
+24V supply voltage
Supply voltage GND
Setpoint GND
(only for 6-wire cable)
Setpoint
0-10V
(or 0-20 / 4-20mA)
Feedback
0-10V
(or 0-20 / 4-20mA)
Control
Analog output:
Only at current output:
max. 500 ohm
PNP when setpoint is reached
(setpoint=feedback)
Shield
=200mA max./4.8W
Inductive
load
M4 connection
on valve body
Connector housing
Digital output:
❉
A 6-wire cable with separate analog ground is used for cable lengths over 2 m to set off the voltage drop for the setpoint.
Pin
Description
5-wire cable
6-wire cable
1
24V voltage supply
brown
brown
2
Analog setpoint input
white
white
3
Supply ground
blue
green
Analog ground
❉
yellow
4
Analog output (feedback)
black
pink
5
Digital output (pressure
switch)
grey
grey
Body
EMC screen
shield
shield