19
OPERATING DESCRIPTION
Signals
The front part of the device is pierced to facilitate contact between the
gas to be detected and the semiconductor-based sensor. The front of the
device is provide with three leds operating as follows:
Push-button P1
Push-button P1 has the following functions:
1. Test function. By pressing the push-button for 4 seconds, the detec-
tor will emit a sound alarm and, upon releasing the push-button, the
test function will be activated offering the possibility of testing the
visual and sound alarms.
The test function includes the following steps:
Activation of the TEST by a BEEP
P
Red led ON for 15 s
P
Yellow led ON for 15 s
P
End of TEST operations by a BEEP
Whereas, by pressing the push-button for 8 seconds at least, after the
first signal the detector will emit another sound alarm . The test function
includes the relay testing.
2. Alarm memory reset. To reset the internal alarm memory signalled by
LED
On
Off
Flashing
detector supplied
detector not
detector under testing
GREEN
with power
power supplied
or sensor being
reactivated
sensor or
detector
YELLOW
detector failure
in full
working order
RED
detector in alarm
detector alarm
stored
condition
off
alarm
C.443BIS 18-12-2003 12:55 Pagina 19