Commissioning
Installation & Commissioning Handbook, User Guide, AutroSafe Interactive Fire Alarm System, P-BSL330/IE,
Autronica Fire and Security AS
Page 18
5.2 Step-by-step Procedure
The commissioning of the BSL-330 module includes the following
steps:
Step
✔
1
Complete the site-specific AutroSafe configuation by means of the AutroSafe
Configuration Tool, including:
- List of detectors / alarm points
- Cause / effect
- AutroCOM port settings (refer to
Setting Parameters / Configuration Program)
- List of panels
- List of other devices
2
Download the Configuration files to AutroSafe.
3
Install and connect the BSL-330 module as described in the previous section.
4
Power up the BSL-330 module - connect the cable from the 24V DC power source
to the connector (Port 1) on the BSL-330 module (refer to the cable connections
overview on the previous page).
5
Verify that the BSL-330 module is properly connected to AutroSafe and that
connection is established.
The 1RX and 1TX indicators should blink at least every 8 seconds.
6
Complete the site-specific PLC configuration, including:
- Cause / effect
- Modbus Register Map versus AutroSafe Unit IO's (from AutroSafe
configuration file "Installation \ UnitName.txt")
- BSL-330 module port 2 settings (refer to
Setting Parameters /
Configuration Program)
7
Do the necessary connections between the external PLC equipment and the
connector (Port 2) on the BSL-330 module.
8
Verify that the BSL-330 module is properly connected to the PLC and that
connection is established.
The 2RX and 2TX indicators should blink at least every 3 seconds.The exact
interval will depend on the PLC's polling period.
9
Verify all critical functions.