Preparing for Commissioning 

Installation & Commissioning Handbook, User Guide, AutroSafe Interactive Fire Alarm System, P-BSL330/IE,  

Autronica Fire and Security AS 

 

Page 13

 

3.5  Setting Parameters / Configuration Program 

The parameter settings for Port 1 

(AutroSafe)

 and Port 2 

(PLC)

 are 

done by means of the KD485 Configuration Program, which is 
delivered with the BSL-330 module.  
 

• 

Make sure that the BSL-330 module is in Executive Mode. The 
EXE indicator should be blinking rapidly. If not, communication is 
not established, and you must repeat the procedure described in 
the previous section (

Entering Executive Mode)

 

• 

Insert the floppy disc into your harddisk drive. 

• 

Dobbelclick on the installation icon, and the Configuration Menu will 
appear on screen. 

 

 

 

• 

Set the baud rate for Port 1 

(AutroSafe)

 to 9 600 baud, 8 bits,  

1 stopbit, even parity (which is the default setup of AutroSafe). 
 
Note that these parameters can be changed for AutroSafe by 
means of the AutroSafe Configuration Tool. 
 

• 

Choose RX Xon/Xoff 

disabled 

(the Xon/Xoff characters to control 

data being received on Port 1) 

• 

Choose TX Xon/Xoff 

disabled 

(the Xon/Xoff characters received by 

BSL-330 control transmitted data on Port 1). 
 

• 

Set the appropriate parameters for Port 2 (external PLC 
equipment) according to the PLC requirement. 

 
 

• 

Click on the highlighted button marked 

Update KD485

 and the 

message 

Writing new KD485 Configuration 

will appear on screen. 

 
When the message disappears, and the 

Update KD485

 button no 

longer is highlighted, all parameters have been set and the 
configuration is completed. 

Not 

to 

be 

used

Summary of Contents for BSL-330

Page 1: ...Interactive Fire Alarm System Installation Commissioning Handbook User Guide Modbus Interface Module BSL 330 AutroCom Protocol Version 1 1 Protecting environment life and property P BSL330 IE...

Page 2: ...bility for any errors that may appear in the publication or for damages arising from the information in it No information in this publication should be regarded as a warranty made by Autronica Fire an...

Page 3: ...t Panel 9 2 5 Dip switches Overview 9 3 Preparing for Commissioning 10 3 1 Introduction 10 3 2 Dip switch Settings 10 3 3 Cable Connections 11 3 4 Entering Executive Mode 12 3 5 Setting Parameters Con...

Page 4: ...4 Modbus Register Mapping 21 5 4 1 Register Allocation Summary 21 5 4 2 Slave Status Register Input Register 1 22 5 4 3 Detector Information Input Registers 48 to 4144 23 5 4 4 Command Register Read...

Page 5: ...uipment Programmable Logic Controllers 1 2 The Reader The handbook is intended to be used by trained service and technical personnel who are responsible for the installation and commissioning of exter...

Page 6: ...IE Autronica Fire and Security AS Page 4 1 4 The Product The BSL 330 module is an RS 232 422 485 interface module used to interface various PLC equipment Programmable Logic Controllers to the AutroSaf...

Page 7: ...Safe Slave Slave Master ON Protocol Converter 1 2 3 4 5 6 TX BSL 330 RX RXB RXA TXB TXA 6 5 4 3 2 1 Power Input Switch External wires convert the BSL 330 s 4 wire RS 485 port to a 2 wire RS 485 port S...

Page 8: ...BV 320 P ASAFE RI DE Installation Handbook Battery Cabinet SY 310 P ASAFE BC DE Commissioning Handbook P ASAFE EE Operator s Handbook Fire Alarm Control Panel BS 310 320 Operator Panel BS 330 P ASAFE...

Page 9: ...cation can be over various serial mediums The one used here is the MODBUS RTU protocol over an RS485 link The communication is set at 9600 baud 8 data bits 1 stop bits and no parity The BSL 330 module...

Page 10: ...to 3V 120 ohm load Power supply 7V to 35V DC 12V DC Input power approx constant at 1 2 watts startup current 300 600mA depending on model At startup the supply voltage must reach 7V in 1 sec Isolation...

Page 11: ...xternal PLC equipment Blinking light 2 seconds intervals indicates that signals are being received Red LED Send TX Port 1 to EAU 321 AutroSafe Blinking light 2 seconds intervals indicates that signals...

Page 12: ...s serial port The BSL 330 module must be set to Executive Mode The required parameters must be set 3 2 Dip switch Settings The illustration below shows the dip switch settings on the BSL 330 module S...

Page 13: ...AS Page 11 3 3 Cable Connections Before entering Executive Mode and setting the required parameters the necessary cabling must be done Consult the cable drawing below Connect the cable from the 24V DC...

Page 14: ...ort 1 which has to be set to Executive Mode To enter Executive Mode press and hold down the green Executive Mode button on the front panel approximately 5 seconds until the EXE indicator starts blinki...

Page 15: ...stallation icon and the Configuration Menu will appear on screen Set the baud rate for Port 1 AutroSafe to 9 600 baud 8 bits 1 stopbit even parity which is the default setup of AutroSafe Note that the...

Page 16: ...g Handbook User Guide AutroSafe Interactive Fire Alarm System P BSL330 IE Autronica Fire and Security AS Page 14 4 Installation 4 1 Overview The drawing below gives an overview of the screw terminals...

Page 17: ...l inside the AutroSafe Fire Alarm Control Panel BS 320 NOTE If the BSL 330 module is to be removed from the rail gently lift the front end upwards If necessary use a flat screwdriver to open up the DI...

Page 18: ...nection to the external PLC equipment Consult the cable overview drawing below Connect the cable from the Serial Port Interface Board EAU 321 inside the AutroSafe BS 320 to the connector Port 1 on the...

Page 19: ...d Communications can be over various serial mediums The one used here is the MODBUS RTU protocol over an RS485 link The PLC takes action on some or all of the status messages from AutroSafe The illust...

Page 20: ...source to the connector Port 1 on the BSL 330 module refer to the cable connections overview on the previous page 5 Verify that the BSL 330 module is properly connected to AutroSafe and that connectio...

Reviews: